CYCLE |
|||||||||
|
In the upper right part you can see a copy of the device front panel, which is updated in real time with the same displays. The button has the same function as the real one. To enter commissioning mode the device has been placed in MANUAL SHUTDOWN, thus to start the cycle: click the button. |
|||||||||
|
In this mode, the transition between stages does not occur at the expiry of the set time but with manual request, with the exception of the ignition phase for which the set safety time is maintained.
|
|||||||||
|
Therefore, after exiting MANUAL SHUTDOWN, the device remains in PREPURGE, allowing any adjustments. To proceed with the cycle, click PRE-IGNITION. |
|||||||||
|
|
|||||||||
|
If the burner has ignited, the keys relating to the stages that can be reached will be activated [5]. The display on the dashboard shows the current phase while the indicators below replicate the display of the status of the outputs. The air valve A can be turned on / off by clicking on the corresponding indicator on the dashboard. The flame signal scale displays both signals marking them with the identifier 1 and 2. If both signals share the same value 3 will be shown. In area [6] there are the following keys:
1 When used as a generic output The status of the process signals is shown in area [7]. |
|||||||||
|
|
|||||||||