VALVE PROVING SYSTEM

The test time to be set for the Valve Proving System depends on the system configuration. By entering the requested data you will obtain the test time to be set in parameters T02 and T05 (before burner ignition) or T12 and T15 (after burner shutdown).


This is the minimum time required, it can be rounded to the nearest higher value or even increased for more stringent control.


According the EN 1643 standard the system shall prevent the opening of the valves when the leakage rate exceeds 0,1% of the burner heat input, starting over 50 dm3/h.

This utility uses the value of 200 dm3/h as max leakage rate.


The following data is required

you can choose whether to USE metric or imperial units

Pu

FUEL INLET PRESSURE

mbar

Q

MAX FLOW RATE (TOTAL BURNER CAPACITY)

m3/h

DN

NOMINAL DIAMETER


L

PIPEWORK LENGTH m

m


The test volume is calculated considering the internal volume of ELEKTROGAS solenoid valves. This data is reported in the field highlighted by the arrow in the images below and can be modified manually if the valves installed have an internal volume different from the one entered automatically.

It is possible to select 4 different pipework configurations.