VALVE PROVING SYSTEM |
|||||||||||||||||
|
The test time to be set for the Valve Proving System depends on the system configuration. By entering the requested data you will obtain the test time to be set in parameters T02 and T05 (before burner ignition) or T12 and T15 (after burner shutdown). This is the minimum time required, it can be rounded to the nearest higher value or even increased for more stringent control. According the EN 1643 standard the system shall prevent the opening of the valves when the leakage rate exceeds 0,1% of the burner heat input, starting over 50 dm3/h. This utility uses the value of 200 dm3/h as max leakage rate.
|
|||||||||||||||||
|
It is possible to select 4 different pipework configurations.
|
|||||||||||||||||
|
|
|||||||||||||||||
|
|
|||||||||||||||||
|
|
|||||||||||||||||