DESCRIPTION TECHNICAL DATA POWER SUPPLY VOLTAGE 115V +10 -15% 230V +10 -15% FREQUENCY 50 … 60 Hz LINE FUSE 4 A 5x20mm SLOW BLOW POWER CONSUMPTION 10 VA MAX OVERVOLTAGE CATEGORY III PURSUANT TO EN 60730 ENVIRONMENT OPERATING TEMPERATURE (-4 … 140 °F) -20 … 60 °C STORAGE TEMPERATURE (-40 … 185 °F) -40 … 85 °C RELATIVE HUMIDITY up to 95%NO CONDENSATION ALLOWED PROTECTION CLASS IP67 DIMENSIONS 201 x 201 x 92 mm MAX WEIGHT 2000 g MOUNTING POSITION ANY THIS UNIT IS NOT INTENDED FOR EXPLOSIVE OR CORROSIVE ENVIRONMENTS OUTPUTS MAX RATED VOLTAGE 250V AC MAX SWITCHING VOLTAGE 270V AC MAX LOAD PER OUTPUT V1 V2 VS VB VA OS 2 A - cosφ = 0.7 PROCESS INPUTS MAX CURRENT PER INPUT G S A HT 3 mA RESPONSE TIME CAN BE ADJUSTED < 1 s FLAME INPUT 1 MINIMUM DETECTABLE CURRENT 1 µA CURRENT LIMITATION 1 mA SENSOR VOLTAGE 250V AC SIGNAL DISPLAY 0…100% (0…30 µA) SENSOR TYPE ELECTRODE AND UV PHOTOTUBE SENSOR LINE LENGTH < 3 m SHARED ROD LINE LENGTH < 2 m PROBE LINE INSULATION MUST BE GREATER THAN 50 MΩ FLAME INPUT 2 MINIMUM DETECTABLE CURRENT 1 µA CURRENT LIMITATION 1 mA SENSOR VOLTAGE 250V AC SIGNAL DISPLAY 0…100% (0…30 µA) SENSOR TYPE UV PHOTOTUBE SENSOR LINE LENGTH < 3 m PROBE LINE INSULATION MUST BE GREATER THAN 50 MΩ ACTUATOR MAX SWITCHING VOLTAGE 300V AC/DC MAX LOAD PER OUTPUT OPEN CLOSE READY 4A @ 250V AC 2A @ 30V DC LIMIT SWITCHES VOLTAGE same as power supply LIMIT SWITCHES CURRENT 3 mA MAX POTENTIOMETER VOLTAGE 5V DC POTENTIOMETER RESISTANCE 100…10000 Ω POTENTIOMETER LINE LENGTH 3 m MAX TraxBus VOLTAGE 30V DC MAX BAUD RATE 4800 9600 19200 38400 FUSE 63…200 mA SUBMINIATURE FUSE