TECHNICAL DATA



POWER SUPPLY

VOLTAGE

115V +10 -15%

230V +10 -15%

FREQUENCY

50 … 60 Hz

LINE FUSE

4 A

5x20mm SLOW BLOW

POWER CONSUMPTION

10 VA MAX

OVERVOLTAGE CATEGORY III PURSUANT TO EN 60730


ENVIRONMENT

OPERATING TEMPERATURE

(-4 … 140 °F)  -20 … 60 °C

STORAGE TEMPERATURE

(-40 … 185 °F)  -40 … 85 °C

RELATIVE HUMIDITY

up to 95%
NO CONDENSATION ALLOWED

PROTECTION CLASS

IP67

DIMENSIONS

201 x 201 x 92 mm MAX

WEIGHT

2000 g

MOUNTING POSITION

ANY

THIS UNIT IS NOT INTENDED FOR EXPLOSIVE OR CORROSIVE ENVIRONMENTS


OUTPUTS

MAX RATED VOLTAGE

250V AC

MAX SWITCHING VOLTAGE

270V AC

MAX LOAD PER OUTPUT

V1 V2 VS VB VA OS

2 A - cosφ = 0.7


PROCESS INPUTS

MAX CURRENT PER INPUT

G S A HT

3 mA

RESPONSE TIME

CAN BE ADJUSTED

< 1 s



FLAME INPUT 1

MINIMUM DETECTABLE CURRENT

1 µA

CURRENT LIMITATION

1 mA

SENSOR VOLTAGE

250V AC

SIGNAL DISPLAY

0…100% (0…30 µA)

SENSOR TYPE

ELECTRODE AND UV PHOTOTUBE

SENSOR LINE LENGTH

< 3 m

SHARED ROD LINE LENGTH

 < 2 m

PROBE LINE INSULATION MUST BE GREATER THAN 50 MΩ



FLAME INPUT 2

MINIMUM DETECTABLE CURRENT

1 µA

CURRENT LIMITATION

1 mA

SENSOR VOLTAGE

250V AC

SIGNAL DISPLAY

0…100% (0…30 µA)

SENSOR TYPE

UV PHOTOTUBE

SENSOR LINE LENGTH

< 3 m

PROBE LINE INSULATION MUST BE GREATER THAN 50 MΩ


ACTUATOR

MAX SWITCHING VOLTAGE

300V AC/DC

MAX LOAD PER OUTPUT

OPEN CLOSE READY

4A @ 250V AC

2A @ 30V DC

LIMIT SWITCHES VOLTAGE

same as power supply

LIMIT SWITCHES CURRENT

3 mA MAX

POTENTIOMETER VOLTAGE

5V DC

POTENTIOMETER RESISTANCE

100…10000 Ω

POTENTIOMETER LINE LENGTH

3 m MAX


TraxBus

VOLTAGE

30V DC MAX

BAUD RATE

4800

9600

19200

38400

FUSE

63…200 mA

SUBMINIATURE FUSE