- The power must be supplied by TN-S power supply systems. For use in ungrounded grid systems or for phase-to-phase systems an isolation transformer with single-side grounding must be installed, the installation of a isolation transformer is recommended for all applications.
- In three-phase systems, always use the same phase for all connections.
- Use power, signal and control cable suitable for the type of operation and complying with all regulations.
- Do not route connections together with frequency converter cables or cables emitting strong electromagnetic fields.
- Provide reliable connection to PE (protection earth) and burner frame, recommended wire gauge > 4 mm2
- Use unscreened high-voltage cable for ignition and ionization rod lines, laying cables individually, avoiding metal conduits. Keep high voltage ignition cables as short as possible, avoiding loops and keep all other cables as far apart as possible.
SAFETY NOTES
- Q2 is a safety device. Under no circumstances should the unit be modified, serviced, or opened. The manufacturer will not assume responsibility for damage resulting from unauthorized modification of the unit.
- Mounting, installation, configuration, commissioning, burner start-up and service must only be carried out by qualified personnel.
- Before performing any work in the connection area of the device, disconnect the unit from the main power supply (all-pole disconnection).
- Protection against electrical shock hazard on the unit and all other connected electrical components must be ensured through proper wiring and grounding practices in accordance with applicable standards (see details in the specific section)..
- • Dropping or impacting the device may cause it to malfunction. Such units should not be operated even if they show no apparent damage.
- Condensation and water ingress into the unit must be prevented.
|
|

|
DISPOSAL
WEEE Directive 2012/19/EU
Waste Electrical and Electronic Equipment Directive
At the end of the product life, dispose of the product in a corresponding recycling center. Do not dispose of the unit with the normal household waste.
|