SAFETY CLASSIFICATION

The Q2 burner controller series is designed for use in industrial combustion systems as set out in "Industrial furnaces and associated processing equipment – Part 2: Combustion and fuel handling systems" (EN ISO 13577-2:2023) and in "Automatic burner control systems for burners and appliances burning gaseous or liquid fuels" (EN 298:2022), when used with gaseous and/or liquid fuels.

The Q2 series devices are suitable for permanent operation (pursuant to EN 298:2022, Section 3.126) and for non-permanent operation (pursuant to EN 298:2022, Section 3.127). 


Type of action

The automatic action corresponds to Type 2 (EN 60730-1:2016+A1:2019+A2:2022+A11:2024, § 6.4.2). The system incorporates three independent switching elements to de-energize the safety-relevant outputs. Loss of supply voltage or detection of an internal fault results in immediate de-energization of all fuel valve outputs.


Behavior under fault conditions

The output signals are switched off in accordance with the criteria of automatic action type B.V.W.AC.AD.AE.AF.AG.AH.AI (pursuant to EN 60730-2-5:2015+A1:2019+A2:2021+AC:2023, § 6.4.3), where:


CODE

MEANING

FUNCTIONALITY IN Q2 SERIES

B

Non-volatile Lock-out

Lockout persists through power cycles, manual reset required.

V

Prepurge

Forced ventilation of the combustion chamber before ignition.

W

Postpurge

Forced ventilation of the combustion chamber after shutdown.

AC

Continuous Supervision

Flame signal is continuously monitored during operation.

AD

Permanent Operation

Suitable for operation exceeding 24 hours without shutdown.

AE

Re-ignition

Immediate ignition attempt upon flame failure during operation.

AF

Recycling

Restart of the full ignition sequence upon flame failure.

AG

Direct Ignition

Ignition of the main burner without a pilot burner.

AI

Intermittent Pilot

Pilot burner remains ignited alongside the main flame.

AH

Interrupted Pilot

Pilot burner is extinguished after main flame stabilization.


Reaction times and Software class

  • Maximum reaction time in the event of a flame failure: This corresponds to the Flame Failure Response Time during operation, configurable between 1 and 10 s.
  • Software class: Corresponds to Software Class C, implemented in a dual-channel architecture with cross-comparison, pursuant to EN 60730-1, Annex H.