STAGE 6 (HIGH TEMPERATURE)

Settings relating to the behavioUr of the burner
in one of the 2 possible STAGES in the high temperature mode

EN 13577-2 § 4.10.3

601 – STAGE DURATION

Duration of the current stage, before proceeding to controlled shutdown:

- ENDLESS, until shutdown or lockout (DEFAULT)
- 1 … 3600 seconds

The transition to a different stage can be requested at any time via remote control.

This could be the stage during only the staged valves are open to have a flameless reaction.

Set ENDLESS when the transition is handled externally (Qio, Fieldbus).

602 – MINIMUM STAGE DURATION

In some processes it is necessary to guarantee the minimum stage duration, it is therefore possible to define a minimum time during which any requests for controlled shutdown will be ignored:

- 0 … 250 seconds (DEFAULT 0)

603 – FUEL VALVES

To adapt operation to different types of process, it is possible to define which fuel valves are active during this stage.

- VS at terminal F4 (DEFAULT ON) 1
- VB at terminal F6 (DEFAULT ON)
- V1 at terminal 06 (DEFAULT OFF)
- V2 at terminal 04 (DEFAULT OFF)

  1. For oil burners this could be the heater outlet.


604 – AIR VALVE

During this stage the air valve can be:

- OFF
- ON (DEFAULT)
- REMOTE CONTROL ONLY

605 – ACTUATOR POSITION

Entering stage 6 it is possible to force the actuator into a predefined position.

- NO ACTION 3 (DEFAULT)
- LO LIMIT SWITCH POSITION 1 
- HI LIMIT SWITCH POSITION 1
- POSITION 1 … 99 % 2 3

  1. Position cannot be changed by remote control
  2. Potentiometer must be connected
  3. Remote command may require a different position

606 – HI-TEMP RELEASE

Behaviour on release of the high temperature signal at the HT terminal.

- GO TO SHUTDOWN
- Go TO STAGE 0 (pre-ignition)
- Go TO STAGE 2 (DEFAULT)
- Go TO STAGE 3
- Go TO STAGE 4

EN298 § 7.101.6.2

607 – AIR FAILURE BEHAVIOUR

Behaviour to the loss of air pressure during this stage (after possible postcombustion and postpurge).

- LOCKOUT (DEFAULT)
- RECYCLE (restarts from pre-operations)

EN298 § 7.101.2.2

608 – FUEL FAILURE BEHAVIOUR

Determines the behaviour at fuel loss during this stage (after possible postcombustion and postpurge).

- LOCKOUT (DEFAULT)
- RECYCLE (restarts from pre-operations)

EN298 § 7.101.2.2

609 – AIR PRESSURE RESPONSE TIME

If the air valve is active in this stage (parameter 604) the contact of the air pressure switch must be closed, if it remains open for a time greater than that set with this parameter, the air loss failure will lead to the behaviour set with parameter 607.

If the air valve is disabled in this stage (parameter 604) the contact of the air pressure switch must be open, if it remains closed for a time longer than the one set with this parameter, the air simulation failure will lead to the behaviour set with parameter 607.

- DISABLED (DEFAULT)
- 1 … 25 seconds

610 – FUEL PRESSURE RESPONSE TIME

During this stage the fuel must flow and therefore the relative pressure switch must be closed, if it remains open for a time longer than the one set with this parameter, the behaviour will depend on the settings of parameter 608.

- DISABLED (DEFAULT)
- 1 … 25 seconds