POSTCOMBUSTION Settings that define the behavioUr of the device |
|
|
|
Y01 – ALLOWED POST-COMBUSTION TIME The flame could still persist after the valves have been closed due to the residual fuel present in the pipes, it is therefore possible to define a period during which the presence of the flame is tolerated: - 0 … 250 seconds (DEFAULT 20) |
|
|
Y02 – AIR VALVE During this stage the air valve can be: - OFF |
|
|
Y03 – ACTUATOR POSITION Entering post-combustion it is possible to force the actuator into a predefined position. - NO ACTION 3 (DEFAULT)
|
|
|
Y04 – FLAME DETECTORS Select which sensors monitor the presence of flame during postcombustion. - FLAME 1 at terminal 10 (UV sensor or electrode) EN298 § 3.108 – § 7.101.2.9 |
|
|
Y05 – AIR PRESSURE RESPONSE TIME If the air valve is active during this stage (parameter Y02) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout. If the air valve is disabled in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout. - DISABLED (DEFAULT) |
|
|
Y06 – IGNITOR In the case of oil burner it could be useful to activate the ignitor to ensure the combustion of any fuel residues. - OFF (DEFAULT) A shared electrode cannot be used for ignition and flame detection when the ignitor is activated during postcombustion. |