POSTCOMBUSTION

Settings that define the behavioUr of the device
after a sTOP request, waiting for the flame to quench

Y01 – ALLOWED POST-COMBUSTION TIME

The flame could still persist after the valves have been closed due to the residual fuel present in the pipes, it is therefore possible to define a period during which the presence of the flame is tolerated:

- 0 … 250 seconds (DEFAULT 20)

Y02 – AIR VALVE

During this stage the air valve can be:

- OFF
- ON (DEFAULT)
- REMOTE CONTROL ONLY

Y03 – ACTUATOR POSITION

Entering post-combustion it is possible to force the actuator into a predefined position.

- NO ACTION 3 (DEFAULT)
- LO LIMIT SWITCH POSITION 1 
- HI LIMIT SWITCH POSITION 1
- POSITION 1 … 99 % 2 3

  1. Position cannot be changed by remote control
  2. Potentiometer must be connected
  3. Remote command may require a different position

Y04 – FLAME DETECTORS

Select which sensors monitor the presence of flame during postcombustion.

- FLAME 1 at terminal 10 (UV sensor or electrode)
- FLAME 2 at terminal 11 (UV sensor)
- FLAME 1+2 (DEFAULT)

EN298 § 3.108 – § 7.101.2.9

Y05 – AIR PRESSURE RESPONSE TIME

If the air valve is active during this stage (parameter Y02) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout.

If the air valve is disabled in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout.

- DISABLED (DEFAULT)
- 1 … 25 seconds

Y06 – IGNITOR

In the case of oil burner it could be useful to activate the ignitor to ensure the combustion of any fuel residues.

- OFF (DEFAULT)
- ON

A shared electrode cannot be used for ignition and flame detection when the ignitor is activated during postcombustion.