STAGE 5 (HIGH TEMPERATURE TRANSITION) Settings relating to the behavioUr of the burner EN 13577-2 § 4.10.3 |
|
|
|
501 – STAGE DURATION Duration of the current stage, before proceeding to the next. - ENDLESS, until shutdown or lockout The transition to a different stage can be requested at any time via remote control. This could be the stage during which all the valves are closed to quench the flame (without the need for a shutdown and recycle) so that when the staged valves open, there is no longer a flame attached to the burner head. Set ENDLESS when the transition is handled externally (Qio, Fieldbus). |
|
|
502 – MINIMUM STAGE DURATION In some processes it is necessary to guarantee the minimum stage duration, it is therefore possible to define a minimum time during which any requests for controlled shutdown will be ignored. - 0 … 250 seconds (DEFAULT 0) |
|
|
503 – FUEL VALVES To adapt operation to different types of process, it is possible to define which fuel valves are active during this stage. This could be an intermediate stage in which different settings are defined before moving on to the high temperature operation stage. - VS at terminal F4 (DEFAULT ON) 1
|
|
|
504 – AIR VALVE During this stage the air valve can be: - OFF |
|
|
505 – ACTUATOR POSITION Entering stage 5 it is possible to force the actuator into a predefined position. - NO ACTION 3 (DEFAULT)
|
|
|
506 – HI-TEMP RELEASE Behaviour on release of the high temperature signal at the HT terminal. - GO TO SHUTDOWN (DEFAULT) EN298 § 7.101.6.2 |
|
|
507 – AIR FAILURE BEHAVIOUR Behaviour to the loss of air pressure during this stage (after possible postcombustion and postpurge). - LOCKOUT (DEFAULT) EN298 § 7.101.2.2 |
|
|
508 – FUEL FAILURE BEHAVIOUR Determines the behaviour at fuel loss during this stage (after possible postcombustion and postpurge). - LOCKOUT (DEFAULT) EN298 § 7.101.2.2 |
|
|
509 – AIR PRESSURE RESPONSE TIME If the air valve is active in this stage (parameter 504) the contact of the air pressure switch must be closed, if it remains open for a time greater than that set with this parameter, the air loss failure will lead to the behaviour set with parameter 507. If the air valve is disabled in this stage (parameter 504) the contact of the air pressure switch must be open, if it remains closed for a time longer than the one set with this parameter, the air simulation failure will lead to the behaviour set with parameter 507. - DISABLED (DEFAULT) |
|
|
510 – FUEL PRESSURE RESPONSE TIME During this stage the fuel must flow and therefore the relative pressure switch must be closed, if it remains open for a time longer than the one set with this parameter, the behaviour will depend on the settings of parameter 508. - DISABLED (DEFAULT) |