STAGE 4 (LOW TEMPERATURE)

Settings relating to the behavioUr of the burner
in one of the 3 possible STAGES in the low temperature mode

EN 13577-2 § 4.10.2

401 – STAGE DURATION

Duration of the current stage, before proceeding to controlled shutdown.

- ENDLESS, until shutdown or lockout (DEFAULT)
- 1 … 3600 seconds

The transition to a different stage can be requested at any time with a remote control.

In 2-stage burners this is typically the main-only condition.

Set ENDLESS when the transition is handled externally (Qio, Fieldbus).

402 – MINIMUM STAGE DURATION

In some processes it is necessary to guarantee the minimum stage duration, it is therefore possible to define a minimum time during which any requests for controlled shutdown will be ignored.

- 0 … 250 seconds (DEFAULT 2)

403 – FUEL VALVES

To adapt operation to different types of process, it is possible to define which fuel valves are active during this stage.

In 2-stage burners this is typically the main-only condition.

- VS at terminal F4 (DEFAULT ON) 1
- VB at terminal F6 (DEFAULT OFF)
- V1 at terminal 06 (DEFAULT OFF)
- V2 at terminal 04 (DEFAULT ON)

  1. For oil burners this could be the heater outlet.


404 – AIR VALVE

During this stage the air valve can be:

- OFF
- ON (DEFAULT)
- REMOTE CONTROL ONLY

405 – ACTUATOR POSITION

Entering stage 4 it is possible to force the actuator into a predefined position.

- NO ACTION 3 (DEFAULT)
- LO LIMIT SWITCH POSITION 1 
- HI LIMIT SWITCH POSITION 1
- POSITION 1 … 99 % 2 3

  1. Position cannot be changed by remote control
  2. Potentiometer must be connected
  3. Remote command may require a different position

406 – FLAME DETECTORS

Select which sensors monitor the presence of flame during this stage.

- FLAME 1 at terminal 10 (UV sensor or electrode)
- FLAME 2 at terminal 11 (UV sensor) (DEFAULT)
- FLAME 1+2

407 – FLAME FAILURE BEHAVIOUR

Determines the behaviour at flame loss during this stage (after possible postpurge). The setting is to be determined on the basis of burner capacity and relevant application standards.

- LOCKOUT (DEFAULT)
- RESPARK (restarts from pre-ignition) 1
- RECYCLE (restarts from pre-operations)

  1. For oil burners with fuel flow rate > 30kg/h any ignition restoration is not allowed

EN298 § 7.101.2.3 – EN13577-2 § 4.11.9

408 – AIR FAILURE BEHAVIOUR

Behaviour to the loss of air pressure during this stage (after possible postcombustion and postpurge).

- LOCKOUT (DEFAULT)
- RESPARK (restarts from pre-ignition) 1
- RECYCLE (restarts from pre-operations)

  1. For oil burners with fuel flow rate > 30kg/h any ignition restoration is not allowed

EN298 § 7.101.2.2

409 – FUEL FAILURE BEHAVIOUR

Determines the behaviour at fuel loss during this stage (after possible postcombustion and postpurge).

- LOCKOUT (DEFAULT)
- RESPARK (restarts from pre-ignition) 1
- RECYCLE (restarts from pre-operations)

  1. For oil burners with fuel flow rate > 30kg/h any ignition restoration is not allowed

EN298 § 7.101.2.2

410 – FLAME FAILURE RESPONSE TIME

If the flame fails during this stage, the fuel valves are switched off within this safety time which must comply with the relevant standards.

- 1 … 10 seconds (DEFAULT 1)

EN298 § 3.105.1 – § 7.101.3.4.3 – § 7.101.3.7 – NFPA86 § 3.3.19.

411 – AIR PRESSURE RESPONSE TIME

If the air valve is active in this stage (parameter 404) the contact of the air pressure switch must be closed, if it remains open for a time greater than that set with this parameter, the air loss failure will lead to the behaviour set with parameter 408.

If the air valve is disabled in this stage (parameter 404) the contact of the air pressure switch must be open, if it remains closed for a time longer than the one set with this parameter, the air simulation failure will lead to the behaviour set with parameter 408.

- DISABLED (DEFAULT)
- 1 … 25 seconds

412 – FUEL PRESSURE RESPONSE TIME

During this stage the fuel must flow and therefore the relative pressure switch must be closed, if it remains open for a time longer than the one set with this parameter, the behaviour will depend on the settings of parameter 409.

- DISABLED (DEFAULT)
- 1 … 25 seconds