SAFETY INTEGRITY LEVEL

Although EN ISO 13577-4 offers procedural simplification (exempting devices already compliant with product standards such as EN 298 from the requirements of IEC 61511, IEC 62061, and ISO 13849), this regulatory flexibility does not address the challenges posed by the most demanding industrial applications.


In High Demand applications, where safety functions are frequently stressed, simple compliance with EN 298 is no longer sufficient to guarantee the reliability expected by Tier-1 operators. In these scenarios, SIL 3 is the definitive benchmark for safety: this level cannot be merely assumed; it requires a rigorous assessment verified by a Notified Body in accordance with Annex J of EN 13611.


The SIL 3 certification simplifies the integration of Q2 into complex systems that require functional safety verification according to IEC 61511, allowing its use without the need for any device risk analysis.


Suitable for Safety Integrity Level

UP TO SIL 3

Type of subsystem

Type B

EN 61508-2:2010

Mode of operation

High demand mode
EN 61508-4:2010

MTTFD
MEAN TIME TO DANGEROUS FAILURE

> 367.600.000 hours

MORE THAN 41 YEARS, 8 mONTHS

 INDIVIDUAL SAFETY FUNCTIONS

PFHD 

SFF

SF-1 FLAME SURVEILLANCE

direct surveillance

low temperature mode

a.        FLAME LOSS

b.        ILLEGAL FLAME
       During purge phases

2,72 x 10-9 1/h

98,85%

SF-1 FLAME SURVEILLANCE

HTO indirect surveillance

high temperature mode

a.        FLAME LOSS

2,59 x 10-9 1/h

98,97%

SF-2 GAS LEAKAGE

a.        TIGHTNESS TEST

b.        NORMAL OPERATION

fuel pressure switch detecting an 

incoherent condition

2,59 x 10-9 1/h

98,97%


SFF (Safe Failure Fraction) indicates the proportion of total failures of a component or system that occur in a safe manner, meaning without causing additional hazard.


PFHD (Probability of Dangerous Failure per Hour) quantifies the probability of a dangerous failure occurring within one hour.