PROOF OF CLOSURE

For applications subject to NFPA 85 (Hazard Code for Boilers and Combustion Systems) and NFPA 86 (Standard for Ovens and Furnaces) and for applications described in EN13577-2 ยง 4.3.6 compliant with ISO 13577-4.

This feature is known by several names:

  • Proof of Closure (POC) 
  • Closed Position Indicator (CPI)
  • Fuel valve end switch (FVES)

Parameter G09 allows you to define the maximum time within which the activation or deactivation of the VS valve (terminal F4) must be confirmed by the limit switch placed on the valve itself (terminal F3).

If the status is inconsistent, the device performs a specific failure lockout.


Connect the F3-F4 terminals together when the VS valve is not equipped with the limit switch S.


WITH

PROOF OF CLOSURE LIMIT SWITCH

WITHOUT

PROOF OF CLOSURE LIMIT SWITCH