LAYOUT |
||
|
The test volume changes as the burner configuration changes. Here are 4 typical applications. |
||
|
|
|
|
|
|
|
|
|
Single stage burner In addition to the safety valve, there is only one fuel valve. The test is carried out for these two valves and the connecting pipework, the discharge takes place directly in the combustion chamber. If the safety valve does not have the proof of closure limit switch S, a jumper must be made between terminals F3-F4. |
|
Single stage burner + exhaust In addition to the safety valve, there is a fuel valve and a valve used for venting into the atmosphere. Testing is done for these valves and the connecting pipework. If the safety valve does not have the proof of closure limit switch S, a jumper must be made between terminals F3-F4. |
|
|
|
|
|
|
|
|
|
Dual stage burner In addition to the safety valve, there are 2 fuel valves. The test is carried out for these two valves and the connecting pipework, the discharge takes place directly in the combustion chamber. If the safety valve does not have the proof of closure limit switch S, a jumper must be made between terminals F3-F4. |
|
Dual stage burner + exhaust In addition to the safety valve, there are 2 fuel valves and a valve used for venting into the atmosphere. Testing is done for these valves and the connecting pipework. If the safety valve does not have the proof of closure limit switch S, a jumper must be made between terminals F3-F4. |