PREPURGE

Settings that define the behavioUr during prepurge of combustion chamber

EN298 § 3.114  –  7.101.3.2 – § 7.101.3.3 – EN 13577-2 § 4.11.1

For burner without fans is the waiting time

EN298 § 3.124.1 – § 3.124.2

P01 – AIR RUN-UP DELAY

To compensate for the delayed air flow due to distant or slow opening valves or to the time required for the fan to reach the necessary flow rate, it is possible to set a waiting time.

- 0 … 3600 seconds (DEFAULT 0)

P02 – AIR VALVE

During this stage the air valve can be:

- OFF
- ON (DEFAULT)

Initially the air valve will be deactivated anyway for a while to verify the correct operation of the pressure switch (air simulation test).

Remote control is disabled.

P03 – ACTUATOR POSITION

When the prepurge starts, it is possible to force the actuator into a predefined position.

The pre-purge time starts after reaching the required position.

- NO ACTION 3
- LO LIMIT SWITCH POSITION 1 
- HI LIMIT SWITCH POSITION 1 (DEFAULT)
- POSITION 1 … 99 % 2 3

  1. Position cannot be changed by remote control
  2. Potentiometer must be connected
  3. Remote command may require a different position

P04 – PREPURGE TIME

Set prepurge time in forced draught burners according to relevant standards (EN 676).

- O … 6000 seconds (DEFAULT 30)

During this time the flame simulation test is carried out.

The time starts when the actuator reaches the required position.

EN298 § 3.124.1 – § 3.124.2 – § 3.124.3 – § 3.124.4
EN13577-2 §4.11.1 – NFPA86 §3.3.59

P05 – AIR PRESSURE RESPONSE TIME

If the air valve is active in this stage (parameter P02) the purge time will be counted only when the contact of the air pressure switch is closed for a time longer than that set with this parameter.

If the contact is open for a time longer than that set with this parameter there will be an air loss lockout.

If the air valve is disabled in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout.

The input can also be used to pause the cycle progress while waiting for external consent to proceed with the pre-purge.

- DISABLED (DEFAULT)
- 1 … 25 seconds

P06 – FUEL PRESSURE RESPONSE TIME

During this stage the fuel flow is stopped and the relative pressure switch must therefore be inactive, but a residual presence could be detected. This parameter allows you to define the maximum time within which the presence of fuel must no longer be detected before a lockout occurs.

- DISABLED (DEFAULT)
- 1 … 25 seconds

P07 – FLAME DETECTORS

During the prepurge it is possible to carry out the flame simulation test, it is therefore necessary to define which sensors are active in this stage to detect an illegal flame.

- NONE
- FLAME 1 at terminal 10 (UV sensor or electrode)
- FLAME 2 at terminal 11 (UV sensor)
- FLAME 1+2 (DEFAULT)

EN298 § 3.108 – § 7.101.2.9

P08 – IGNITOR

The relevant standards require that for oil burners the ignitor is active during prepurge.

- OFF (DEFAULT)
- 1 … 25 seconds

A shared electrode cannot be used for ignition and flame detection when the ignitor is activated during prepurge.

EN298 § 7.101.3.3