PREIGNITION (STAGE 0) Settings relating to the STAGE preceding burner ignition EN298 § 3.135.2 |
|
|
|
001 – STAGE DURATION Duration of preignition, before proceeding to ignition. - 500 milliseconds (DEFAULT) The ignitor is turned on before the start of the ignition stage to check its correct functioning before delivering the fuel. The time starts after the actuator has reached the predefined position. For systems that give more than one ignition attempt, set this time as an inter-purge or inter-wait time after an unsuccessful ignition attempt. EN298 § 7.101.2.8 |
|
|
002 – AIR VALVE During this stage the air valve can be: - OFF |
|
|
003 – ACTUATOR POSITION Before starting the ignition stage, it is possible to force the actuator into a predefined position. - NO ACTION 3
|
|
|
004 – AIR PRESSURE RESPONSE TIME If the air valve is active during this stage (parameter 002) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout. If the air valve is disabled in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout. - DISABLED (DEFAULT) |
|
|
005 – FUEL PRESSURE RESPONSE TIME During this stage the pressure switch must detect the fuel, lockout occurs if the fuel pressure is not detected within the time specified with this parameter. The input can also be used to pause the cycle progress while waiting for external consent to proceed with the ignition. - DISABLED (DEFAULT) |
|
|
006 – IGNITOR Select if the burner is ignited with a spark generated by a high voltage transformer or if this output should remain inactive during this stage. - OFF |