IGNITION (STAGE 1)

Settings relating to the burner ignition TRIAL

EN298 § 3.135.3 – EN13577-2 § 4.11.4

101 – STAGE DURATION

Duration of the ignition stage.

(First Safety Time / Trial for Ignition Period).

- 1 … 25 seconds (DEFAULT 3)

It must be set according to EN 13577-2 (or other relevant requirements):


Natural draught burners

≤ 350 kW → 10”

> 360 kW → 5"

MAX IGNITION POWER MUST BE ≤ 33% NOMINAL POWER

WITH MAXIMUM OF 350 kW

Forced and induced draught burners

≤ 70 kW → 5”

> 70 kW → 3"

MAX IGNITION POWER MUST BE ≤ 120 kW


EN298 § 3.116 – EN13577-2 § 4.11.5 §4.11.6 §4.11.7 – NFPA86 § 3.3.72

102 – FUEL VALVES

To adapt operation to different types of process, it is possible to define which fuel valves are active during the ignition trial.

- VS at terminal F4 (DEFAULT ON) 1
- VB at terminal F6 (DEFAULT OFF)
- V1 valve at terminal 06 (DEFAULT ON)
- V2 valve at terminal 04 (DEFAULT OFF)

  1. For oil burners this could be the heater outlet.

103 – STARTUP ATTEMPTS

When the flame is not detected at the end of the ignition trial, up to 3 attempts can be made as long as the safety of the application is not impaired:

- 1 attempt (DEFAULT)
- 2 attempts
- 3 attempts
- 4 attempts

A lockout will occur if all attempts are completed without flame being detected. 

Set parameter 001 properly if an inter-purge or inter-wait time is required after an unsuccessful ignition attempt.

EN676 § 4.4.1.8 


104 – AIR VALVE

During this stage the air valve can be:

- OFF
- ON (DEFAULT)
- REMOTE CONTROL ONLY

105 – AIR PRESSURE RESPONSE TIME

If the air valve is active during this stage (parameter 002) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout.

If the air valve is disabled in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout.

- DISABLED (DEFAULT)
- 1 … 25 seconds

106 – FUEL PRESSURE RESPONSE TIME

During this stage the fuel must flow and therefore the relative pressure switch must be closed. This parameter allows you to define how long the contact can be detected open before a lockout occurs.

- DISABLED (DEFAULT)
- 1 … 25 seconds

107 – IGNITOR

Select if the burner is ignited with a spark generated by a high voltage transformer or if this output should remain inactive during this stage.

- OFF
- ON (DEFAULT)

108 – FLAME DETECTORS

At the end of the ignition stage the presence of flame is detected, it is therefore necessary to define which sensors are active in this stage.

- FLAME 1 at terminal 10 (UV sensor or electrode)
- FLAME 2 at terminal 11 (UV sensor)
- FLAME 1+2 (DEFAULT)