LEAKAGE RATE

According the EN 1643 standard the system shall prevent the opening of the valves when the leakage rate exceeds 0,1% of the burner heat input, starting over 50 dm3/h.

Recommended max leakage ≤ 200 dm3/h

Example:        With a burner capacity of 100 m3/h, the maximum leakage rate is 100 dm3/h. 

If the burner capacity is 30 m3/h, the maximum leakage rate would be 50 dm3/h.


The effective leakage rate in dm3/h is given from the following equation (EN 13611):





Pu

inlet pressure

Q

max flow rate (total burner capacity) [m3/h]

qL

leakage rate (0,1% of total burner capacity = 0.001∙ Q)

∆PT

difference between inlet pressure and final test pressure [mbar]

equal to 0,5 Pu (fuel pressure switch setting)

VT

test volume [dm3] [liters]

PATM

atmospheric pressure [mbar] = 1013 mbar

tP

test periods [s] T03 T05 T12 T15 (recommended 25s)

to

dis/charge times [s] T01 T04 T11 T13 (recommended 5s)



From the above equation we can derive the duration of the fill test and empty test periods required to detect the maximum permissible leakage:





The total duration of the test is         2 ∙ to + 2 ∙ tp


Test volume

Test volume VT consists of inner volume of outlet chamber of upstream valve + inlet chamber of all downstream valves + pipework volume. The table shows the internal volumes of the valves1 and the volume for each meter of pipe referred to different nominal diameters.


  1. The data refer to valves manufactured by Delta Elektrogas, the correct data must be obtained from the documentation of the valve manufacturer.


Nominal

Diameter

Valve volume

[dm3]

Pipe volume

[dm3/m]

DN10

0.07

0.1

DN15

0.07

0.2

DN20

0.12

0.3

DN25

0.12

0.5

DN32

0.47

0.8

DN40

0.47

1.3

DN50

0.62

2.0

DN65

2.60

3.3

DN80

2.60

5.0

DN100

5.00

7.9

DN125

17.20

12.3

DN150

17.20

17.7

DN200

31.70

31.4


Example

2

valves DN50

= 0,62 dm3

upstream outlet chamber + downstream inlet chamber

1m

pipework

= 2.0 dm3


Pu

inlet pressure

= 100 mbar

∆PT = 0.5 Pu 0 = 50 mbar

Q

max flow rate

= 40 m3/h


qL

leakage rate

= 0.001 Q = 40 dm3/h

increased to minimum 50dm3/h





Set 10 seconds for fill and empty test periods (T03 T05 T12 T15) and pressure switch threshold at 50 mbar.


The Q2 device simplifies installation by integrating both leakage control and minimum pressure detection into a single pressure switch. If you wish to set the pressure switch to a value other than 0,5∙Pu for minimum pressure intervention, you simply need to differentiate the test times:

  • T02 / T12: test times for the downstream valve(s).
  • T05 / T15: test times for the upstream valve.


The following coefficients should be applied to compensate for variations in the pressure switch intervention threshold:


Pressure switch

setting

Test time

downstream

T02 / T12

Test time

upstream

T05 / T15

20%

160%

40%

30%

140%

60%

40%

120%

80%

50%

100%

100%

60%

80%

120%

70%

60%

140%

80%

40%

160%


Times are expressed as percentages relative to the reference time for a standard 50% calibration.


Practical Example

If previous calculations resulted in 10 seconds with Pu = 200 mbar:

  • Setting the intervention point to 100 mbar (50%):
    - T02/T12 = 10 seconds (downstream test)
    - T05/T15 = 10 seconds (upstream test)
  • Setting the intervention point to 60 mbar (30%)
    - T02/T12 = 14 seconds (downstream test)
    - T05/T15 = 6 seconds (upstream test)
  • Setting the intervention point to 140 mbar (70%):
    T02/T12 = 6 seconds (downstream test)
    T05/T15 = 14 seconds (upstream test)

The total test time (excluding filling and emptying phases) always remains 20 seconds.


Notes:

- the upward tripping point of a pressure switch is slightly different from the downward one.

- minimum time that can be set in Q2 is 5 seconds.


A utility for calculating test times is available in the Q.Suite software