|
STAGE 2 (LOW TEMPERATURE) Settings relating to the behavioUr of the burner EN 13577-2 § 4.10.2 |
|
|
|
201 – STAGE DURATION Duration of the current stage, before proceeding to the next. - ENDLESS, until shutdown or lockout The transition to a different stage can be requested at any time via remote control. In multi-stage burners this is the pilot or start flame proving period. Set ENDLESS when the transition is handled externally (Qio, Fieldbus). EN298 § 3.131 |
|
|
202 – MINIMUM STAGE DURATION In some processes it is necessary to guarantee the minimum stage duration, it is therefore possible to define a minimum time during which any requests for controlled shutdown will be ignored. - 0 … 250 seconds (DEFAULT 2) |
|
|
203 – FUEL VALVES To adapt operation to different types of process, it is possible to define which fuel valves are active during this stage. In 2-stage burners this is typically the pilot-only condition. - VS at terminal F4 (DEFAULT ON) 1
|
|
|
204 – AIR VALVE During this stage the air valve can be: - OFF |
|
|
205 – ACTUATOR POSITION Entering stage 2 it is possible to force the actuator into a predefined position. - NO ACTION 3 (DEFAULT)
|
|
|
206 – FLAME DETECTORS Select which sensors monitor the presence of flame during this stage. - FLAME 1 at terminal 10 (UV sensor or electrode) (DEFAULT) |
|
|
207 – FLAME FAILURE BEHAVIOUR Behaviour at flame loss during this stage (after possible postpurge). The setting is to be determined on the basis of burner capacity and relevant application standards. - LOCKOUT (DEFAULT)
EN298 § 7.101.2.3 – EN13577-2 § 4.11.9 |
|
|
208 – AIR FAILURE BEHAVIOUR Behaviour to the loss of air pressure during this stage (after possible postcombustion and postpurge). - LOCKOUT (DEFAULT)
EN298 § 7.101.2.2 |
|
|
209 – FUEL FAILURE BEHAVIOUR Behaviour at fuel loss during this stage (after possible postcombustion and postpurge). - LOCKOUT (DEFAULT)
EN298 § 7.101.2.2 |
|
|
210 – FLAME FAILURE RESPONSE TIME If the flame fails during this stage, the fuel valves are switched off within this safety time which must comply with the relevant standards. - 1 … 10 seconds (DEFAULT 1) EN298 § 3.105.1 – § 7.101.3.4.3 – § 7.101.3.7 – NFPA86 § 3.3.19 |
|
|
211 – AIR PRESSURE RESPONSE TIME If the air valve is active in this stage (parameter 204) the contact of the air pressure switch must be closed, if it remains open for a time greater than that set with this parameter, the air loss failure will lead to the behaviour set with parameter 208. If the air valve is disabled in this stage (parameter 204) the contact of the air pressure switch must be open, if it remains closed for a time longer than the one set with this parameter, the air simulation failure will lead to the behaviour set with parameter 208. - DISABLED (DEFAULT) |
|
|
212 – FUEL PRESSURE RESPONSE TIME During this stage the fuel must flow and therefore the relative pressure switch must be closed, if it remains open for a time longer than the one set with this parameter, the behaviour will depend on the settings of parameter 209. - DISABLED (DEFAULT) |











