language IT | EN  face Welcome Guest | Login
MINI VERSION

Automatic Burner Control Unit for gas and oil burners
Direct ignition 1 stage fuel valve
Intermittent or continuous operation

QBK MINI – 1 stage

• Natural or forced draught gas burners.
• Blue flame oil burners.
• Single stage burners.
• Flame detection by means of UV sensor, dual or single electrode.
• Built-in fieldbus control.
• Infrared commissioning interface (smartphone app).
• Led-bar flame signal indicator.
• Configurable flame sensitivity.
• Advanced self-diagnostic report of cycle status, lockouts and failures.
• Log memory for lockouts and faults.


FRONT PANEL
FITTING SCREWS 1
FLAME SIGNAL BARGRAPH – RED 2
STATUS DISPLAY 3
RESET / SHUTOFF BUTTON 4
COM INDICATOR – YELLOW 5
INTERNAL
8 MAIN TERMINAL BOARD
9 POWER SUPPLY FUSE 1
1 ULTIMATE PROTECTION AGAINST DANGEROUS CONDITIONS BY MEANS OF INTERNAL NON REPLACEABLE 5A SAFETY FUSE
ORDER CODE DESCRIPTION NOTE
1488.30.PM QBK MINI 115 PLASTIC
Power supply 115V
ACTIVE
1488.40.PM QBK MINI 230 PLASTIC
Power supply 230V
ACTIVE
1488.30.0M QBK MINI 115 ALUMINIUM
Power supply 115V
ACTIVE
1488.40.0M QBK MINI 230 ALUMINIUM
Power supply 230V
ACTIVE

ORDER CODE MUST BE COMPLETED WITH CONFIGURATION CODE

PROVIDE RELIABLE CONNECTION TO PE (PROTECTION EARTH) AND BURNER FRAME
RECOMMENDED WIRE GAUGE > 4 mm2


COM INTERFACE – POSITIVE C1
COM INTERFACE – NEGATIVE C2
POWER SUPPLY – N 01
POWER SUPPLY – L 02
03
04
PILOT VALVE – N 05
PILOT VALVE – L 06
IGNITION TRANSFORMER – N 07
IGNITION TRANSFORMER – L 08
GROUND 09
FLAME SENSOR INPUT 10
L EXTERNAL LIMITS
V1 FUEL VALVE
Power supply
  • • Voltage115 or 230 V +10-15%
  • • Frequency50/60 Hz
  • • Line FuseQUICK 3 A
  • • Power Consumption< 6 VA
  • • Power Dissipation< 4 W
Environment
  • • Operating Temperature-20...+60°C
  • • Storage Temperature-40...+85°C
  • • Relative HumidityNO CONDENSATION
  • • Protection ClassIP64 / NEMA3
  • • WeightAPPROX 1100 g
  • • Mounting Position ANY
Outputs
  • • Max rated Voltage250 VAC
  • • Max switching Voltage440 VAC
  • • Max Load (per output)2 A PF=70%
Flame detection
  • • Minimum ionization Current> 1 μA
  • • Current limitation< 3 mA
  • • Signal Display0...100% | 0...30 μA
  • • Detector Line Length< 30 m
  • • Single Rod Line Length< 2 m
  • • Detector Voltage< 250 VAC
  • • Detector Insulation> 50 MΩ
  • • UV SensorUV4SH
TraxBus Com Interface
  • • Voltage< 30 VDC
  • • Baud Rate4800, 9600, 19200, 38400

EXTERNAL FITTING HOLES 1
BREAKABLE FITTING HOLES 2
BREAKABLE PG11 HOLES FOR WIRING 3
BREAKABLE PG9 HOLES FOR WIRING 4
M OPTIONAL PIPE FITTING CLAMP
CAST ALUMINUM ALLOY EN AB 46100 or THERMOPLASTIC POLYMER BLEND UL-V0 OVERALL DIMENSION: 200 x 120 x 71 mm
EXTERNAL COATING GRAY RAL9006

QBK is fully confgurable: the same device can be used to control different types of gas and oil burners. Password is required to modify all parameters except for Communication settings.

Customers that want to modify the configuration can apply for specific agreement here. Once approved, all purchased units will have unique password assigned. Since a new label or remark must be placed on the unit when the original configuration is modified, this procedure is not recommended for occasional users.

Configuration code with default settings (red)


Note on EC type-examination

Since EN 298 does not describe all functions of the QBK – implemented to manage all possible industrial scenarios – the operator is responsible for ensuring that parameters and functions are appropriate for the application.
Certification applies only for options and values allowed by EN-298.