WIRING

The BLACK terminals of the base terminal block [8] are present in all versions, while the GREEN ones (2nd stage and high temperature input) only starting from the Q22 version.


The ORANGE terminals add functions for the Q26 and Q28 versions.


The BLUE terminals associated with the actuator are available in the Q28 version only.




BASE TERMINAL BOARD [8]

11

IN

2ND FLAME INPUT

10

IN

1ST FLAME INPUT

09


GROUND

08

OUT

IGNITOR

07

OUT

NEUTRAL

06

OUT

V1 - PILOT FUEL VALVE

05

OUT

NEUTRAL

04

OUT

V2 - MAIN FUEL VALVE

03

OUT

NEUTRAL

02

IN

POWER SUPPLY PHASE

01

IN

POWER SUPPLY NEUTRAL

C2


TraxBus -

C1


TraxBus +

HT

IN

HIGH TEMPERATURE BYPASS




EXTENDED TERMINAL BOARD [9]

S2

OUT

NEUTRAL

S1

OUT

ELECTRO OPTICAL SHUTTER

A4

OUT

NEUTRAL

A3

OUT

VA - AIR VALVE

A2

IN

AIR PRESSURE SWITCH

A1

OUT

PHASE

F7

OUT

NEUTRAL

F6

OUT

VB - BYPASS VALVE

F5

OUT

NEUTRAL

F4

OUT

VS - SAFETY FUEL VALVE [OH]

F3

IN

PROOF OF CLOSURE SWITCH [OW]

F2

IN

FUEL PRESSURE SWITCH

F1

OUT

PHASE




ACTUATOR TERMINAL BOARD [10]

P3

OUT

POTENTIOMETER (OPEN)

P2

IN

POTENTIOMETER

P1

OUT

POTENTIOMETER (CLOSE)

B8

IN

HI POSITION LIMIT SWITCH

B7

IN

LO POSITION LIMIT SWITCH

B6

OUT

PHASE

B5

IN

POWER SUPPLY

B4

OUT

READY (FREE TO MOVE)

B3

OUT

OPEN

B2

OUT

CLOSE

B1

OUT

NEUTRAL

[OH] FUEL PRE-HEATER (OIL BURNERS)

[OW] HEATHER THERMOSTAT (OIL BURNERS)  


EXTERNAL
LIMITS

FUEL 2
PRESSURE SWITCH

ACTUATOR

(DAMPER)    

1ST STAGE
FUEL VALVE

PROOF OF CLOSURE
SWITCH (VS)

LO POSITION
LIMIT SWITCH

2ND STAGE
FUEL VALVE

SAFETY
FUEL VALVE

HI POSITION
LIMIT SWITCH



MULTIFUNCTIONAL BYPASS VALVE





AIR 1
PRESSURE SWITCH





AIR VALVE

BLOWER





ELECTRO OPTICAL

SHUTTER(S)




1        The air pressure switch input can be used to suspend cycle progress while waiting for
         external consent to proceed with prepurge.


2        The fuel pressure switch input can be used to suspend cycle progress while waiting for

external consent to proceed with ignition.