TECHNICAL DATA



POWER SUPPLY

VOLTAGE

100 ... 240VAC

FREQUENCY

47 … 63 Hz

LINE FUSE

6,3 A

EMBEDDED

POWER CONSUMPTION

6 VA MAX

AUTOMATIC OVERTEMPERATURE AND OVERCURRENT PROTECTION


ENVIRONMENT

OPERATING TEMPERATURE

(-4 … 140 °F)  -20 … 60 °C

STORAGE TEMPERATURE

(-40 … 185 °F)  -40 … 85 °C

RELATIVE HUMIDITY

10 ... 90%
NO CONDENSATION ALLOWED

DIMENSIONS

80 x 90 mm MAX

WEIGHT

90 g

THIS UNIT IS NOT INTENDED FOR EXPLOSIVE OR CORROSIVE ENVIRONMENTS


OUTPUTS

MAX RATED VOLTAGE

250V AC

MAX SWITCHING VOLTAGE

270V AC

MAX LOAD PER OUTPUT

V1 V2 VS VB VA OS

2 A - cosφ = 0.7


PROCESS INPUTS

MAX CURRENT PER INPUT

5 mA

VOLTAGE

PROVIDED BY DEVICE

12VDC



ANALOG OUTPUT

OUTPUT CURRENT

23 mA MAX

LOOP VOLTAGE

12VDC

SPAN ADJUST

4 ... 19,0 mA

4 ... 22,5 mA

LOOP IMPEDANCE

350 Ω MAX