STANDARD IGNITOR

Traditional inductive ignition transformer working at power supply frequency
TRE820PISO – 8 kV, 20mA, 19% duty cycle




TRE820PISO inside

4 PARKER SCREWS 4,2 x 32 mm


TRE820PISO on back side

4 PARKER SCREWS 4,2 x 45 mm


2 independent electrodes 

The high voltage creates a spark between the ignition electrode and burner ground.

The flame current flows from the dedicated electrode into the control unit.


BLUE WIRE

NEUTRAL

CONNECT TO TERMINAL 07

BLACK WIRE

PHASE

CONNECT TO TERMINAL 08

YELLOW GREEN

GROUND

CONNECT TO GROUND

BROWN WIRE

HV RETURN

CONNECT TO GROUND

1 shared electrode 

A single electrode used for both ignition and flame detection.

Electrode switched to ground during the ignition. The flame current flows from the electrode through the secondary winding into the control unit.


BLUE WIRE

NEUTRAL

CONNECT TO TERMINAL 07

BLACK WIRE

PHASE

CONNECT TO TERMINAL 08

YELLOW GREEN

GROUND

CONNECT TO GROUND

BROWN WIRE

HV RETURN

CONNECT TO TERMINAL 10

THE LENGTH OF THE HIGH VOLTAGE CABLE MUST BE WITHIN 2 METERS