IGNITOR |
|
For direct spark ignition, an ignition transformer is required. You may use either of the following types with Q2:
Provide reliable connection between burner frame and internal ground bar or one of the external ground screws of the device, recommended wire gauge > 4 mm2. Use unshielded high voltage cables keeping them as short as possible, avoiding loops, and keep all other cables as far apart as possible. For applications involving frequent activations, the installation of an RC snubber (0.1µF - 100 Ω - 1/2 W - 600 VAC) in parallel with the load (between terminals 07 and 08) is recommended in order to extend the life of the relay contact. Duty cycle The duty cycle indicates for how long the ignition transformer can operate within 180 s. Max operating time = Duty cycle [%] × 180 s / 100% Considering 19% duty cycle of TRE820, the maximum operating time is 34 s within 3 minutes. This means a maximum of two (2) ignition attempts, each with five (5) second duration are allowed per minute to avoid damages. Considering 33% duty cycle of TRK2, the maximum operating time is 60 s within 3 minutes. This means a maximum of four (4) ignition attempts, each with five (5) second duration are allowed per minute to avoid damages. |