STAGE 6 |
|
|
This is the steady state operating condition for a burner working in high temperature mode and is reached at the end of stage 5. The presence of fuel and air can be verified by activating the pressure switches, defining their reaction time (to tolerate any short drops in pressure). |
|
|
|
|
|
This stage usually does not have a predefined duration, but can be terminated by: • manual shutdown • controlled shutdown • HT signal removal (see below) • lockout It is anyway possible to set a duration at the end of which the burner will move to controlled shutdown. |
|
|
It is also possible to define a minimum duration during which any controlled shutdown requests are ignored. Parameter 606 defines the behaviour when the HT signal is removed: • move to controlled shutdown • move to pre-ignition • move to low temperature stage 2 • move to low temperature stage 3 • move to low temperature stage 4 |
|
|
The transition to any other high temperature stage can be managed with remote control. Parameters 607 and 608 define the behaviour in the event of air pressure failure and fuel pressure failure: • lockout • re-ignition • recycle from the beginning After post-purge stage, if set and due. |
|
|
The actuator position can be preset and even changed remotely.
|
|
|
The LED 100 of the flame signal bargraph is blinking when in high temperature mode. |
|
|
Allowed remote commands H R S s A a O o f L D d Dxx