POST COMBUSTION |
|
|
After a shutdown request or an anomaly that leads to a lockout from low temperature stages, the flame may not quench immediately and it is possible to define the maximum duration of this period during which the presence of the flame is tolerated. The fuel valves are off while the behaviour of the air valve can be defined. The air pressure switch can be enabled to detect air failure or air simulation, also defining the response time (to tolerate any short drops in pressure). |
|
|
|
|
|
The actuator position can be preset and even changed remotely. In this stage it can be defined which sensors will detect the presence of the flame, possibly activating the ignitor (for liquid fuels). If the ignition transformer is activated in this stage, it will not be possible to use a shared electrode for ignition and flame detection. |
|
|
|
|
|
When the flame signal disappears, the shutdown cycle proceeds to the post-operation stage. An immediate lockout occurs if the flame does not quench within the set time. |
|
|
|
|
|
POST-OPERATION is performed if a lockout cause occurs during POSTCOMBUSTION, while a failure will lead to immediate lockout (because the information for managing the process are no longer reliable). |
|
|
Allowed remote commands H R S s A a O o f L D d Dxx |
|