PRE IGNITION (STAGE 0) |
|
|
This is the stage before the ignition of the burner. The FUEL SAFETY VALVE is active while the other fuel valves are closed and it is possible to define the behaviour of the AIR valve. The air pressure switch can be enabled to detect air failure or air simulation, depending on air output setting. |
|
|
If the fuel pressure switch is enabled, it must detect the presence of fuel within the set time, otherwise a lockout will occur. |
|
|
Response times of the air and fuel pressure switches are adjustable to tolerate short drops or spikes. The ignition transformer is activated to verify the correct operation of the output before proceeding to open the fuel valves. The actuator is moved to the predefined position for the ignition. If the actuator position is set to 0% (limit switch position) it cannot be changed remotely. |
|
|
|
|
|
When the actuator has reached the predefined ignition position and the time set for the pre-ignition phase has elapsed, the cycle continues with the next stage.
|
|
|
If the HT input is active, direct flame monitoring is disabled and the cycle proceeds directly to stage 5. |
|
|
|
|
|
Allowed remote commands H R S s A a O o f L D d |
|