PRE OPERATION |
|
|
Before starting the ignition cycle, the efficiency of the air pressure switch is verified: the air valve is off and within 60 seconds the air pressure switch contact must be open. The correct functioning of the relays is verified, the ignitor light turns on for a short instant (but the output remains off). |
|
|
|
|
|
With the start of the cycle, the preparatory stage is entered. It is possible to activate the fuel valve tightness test which is carried out before the predefined pre-purge time. Any manual shutdown requests from the button are ignored during the fuel valve tightness test. |
|
|
|
|
|
A possible delay of the air pressure introduced by blower run-up can be compensated by introducing a waiting time. |
|
|
|
|
|
The prepurge time can be set and starts counting once the actuator has reached the set position. If the actuator position is set to 100% (limit switch position) it cannot be changed remotely. |
|
|
|
|
|
The fuel valves are off while it is possible to define the behaviour of the air valve which can be controlled via the air pressure switch: with the air valve off there will be a lockout in the event of presence (simulation), while with an active air valve there will be a lockout in the absence of air for a time longer than the one set. The purge time is counted only when the presence of air is detected by the pressure switch or flow switch. |
|
|
|
|
|
The fuel pressure switch can be enabled to detect unwanted fuel presence or pressure switch failure. Response times of the air and fuel pressure switches are adjustable to tolerate short drops or spikes. The prepurge stage can be interrupted by a Manual Shutdown request through the button. The blue display cycles as the prepurge time is running. |
|
|
|
|
|
The flame surveillance should be activated for all installed sensors to identify possible flame simulation (illegal detection), for liquid fuels the ignitor should also be activated. If the ignition transformer is active in this stage, it will not be possible to use a shared electrode for ignition and flame detection. |
|
|
Allowed remote commands H R S s O o f L D d |
|