IGNITION (STAGE 1)

This is the safety time during which the fuel can be introduced into the combustion chamber while waiting for the flame to form. The duration is ruled by specific standards and can be set.


The behaviour of all fuel valves and the air valve can be defined.

The air pressure switch can be enabled to detect air failure or air simulation, depending on air output setting.

The fuel pressure switch can be enabled to detect fuel failure.

Response times of the air and fuel pressure switches are adjustable to tolerate short drops or spikes.


The actuator remains in the position reached in the previous step and cannot be controlled remotely.


The ignitor is usually activated, but it is also possible to deactivate it.


If the flame is detected by one or both of the selected sensors, the burner has ignited correctly and the cycle continues to stage 2, otherwise lockout occurs due to ignition failure.




The standards allow in some cases to make up to a maximum of 3 further ignition attempts, the number of attempts can be set within this range.


Allowed remote commands

H R S s A a O o f L D d