POWER ON

Settings that define the behavioUr of the device
after being powered

S01 – POWER-ON BEHAVIOUR

This parameter defines the behaviour of the device at power on, once the self-test has been successfully completed:

- AUTOSTART: cycle starts automatically (DEFAULT) 1
- STANDBY: push the button / remote control to start cycle 
- MONITOR: detects the flame, no cycle (like a flame relay)

1        Unless the unit has been turned off while in lockout (non-volatile)

EN298 § 3.121.1

S02 – AIR VALVE

During this stage the air valve can be:

- OFF (DEFAULT)
- ON
- REMOTE CONTROL ONLY

S03 – ACTUATOR POSITION

When the device is powered, it is possible to force the actuator into a predefined position:

- NO ACTION 3 (DEFAULT)
- LO LIMIT SWITCH POSITION 1
- HI LIMIT SWITCH POSITION 1
- POSITION 1 … 99 % 2 3

  1. Position cannot be changed by remote control
  2. Potentiometer must be connected
  3. A different position can be requested with remote control

S04 – AIR PRESSURE RESPONSE TIME

If the air valve is active during this stage (parameter S02) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout.

If the air is inactive in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout.

- DISABLED (DEFAULT)
- 1 … 25 seconds