POWER ON Settings that define the behavioUr of the device |
|
|
|
S01 – POWER-ON BEHAVIOUR This parameter defines the behaviour of the device at power on, once the self-test has been successfully completed: - AUTOSTART: cycle starts automatically (DEFAULT) 1 1 Unless the unit has been turned off while in lockout (non-volatile) EN298 § 3.121.1 |
|
|
S02 – AIR VALVE During this stage the air valve can be: - OFF (DEFAULT) |
|
|
S03 – ACTUATOR POSITION When the device is powered, it is possible to force the actuator into a predefined position: - NO ACTION 3 (DEFAULT)
|
|
|
S04 – AIR PRESSURE RESPONSE TIME If the air valve is active during this stage (parameter S02) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout. If the air is inactive in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout. - DISABLED (DEFAULT) |