POST OPERATION |
|
|
Once the flame is quenched, some final activities can be performed. It is possible to activate the fuel valve tightness test which is carried out before the post-purge. Any manual shutdown requests from the button are ignored during the fuel valve tightness test. |
|
|
|
|
|
The postpurge time can be set and starts counting once the actuator has reached the set position. If the actuator position is set to 100% (limit switch position) it cannot be changed remotely. |
|
|
|
|
|
The fuel valves are off while it is possible to define the behaviour of the air valve which can be controlled via the air pressure switch: with the air valve off there will be a lockout in the event of presence (simulation), while with an active air valve there will be a lockout in the absence of air for a time longer than the one set. The purge time is counted only when the presence of air is detected by the pressure switch or flow switch. Response time of the air pressure switch is adjustable to tolerate short drops or spikes. |
|
|
|
|
|
The postpurge stage cannot be interrupted by a Manual Shutdown request through the button. The blue display cycles as the postpurge time is running. Postpurge always completes and cannot be stopped. |
|
|
|
|
|
The flame surveillance should be activated for all installed sensors to identify possible flame simulation (illegal detection), for liquid fuels the ignitor should also be activated. If the ignition transformer is active in this stage, it will not be possible to use a shared electrode for ignition and flame detection. When all activities have been completed, the controlled shutdown or lockout condition is reached. |
|
|
|
|
|
The time will be completed if a lockout cause occurs during POSTPURGE, while a failure will lead to immediate lockout (because the information for managing the process is no longer reliable). |
|
|
Allowed remote commands H R S s O o f L D d |
|