When a burner remains operative consecutively for more than 24 hours without shutdown, the flame monitoring system must be suitable for permanent operation according to the provisions of EN298 § 7.101.4.1.2. Q2 performs continuous self-tests of the flame monitoring circuitry and a periodic check on sensors and is suitable for permanent operation. There are no additional requirements for sensing flame with ionization electrodes, according to the provisions of EN298 7.101.4.1.3 For permanent operation of UV phototubes an electro-optical shutter wired at terminals S1-S2 is required, according to the provisions of EN298 § 7.101.4.1.5 and § 7.101.4.1.2. Parameter G07 allows you to activate this function for one or both sensors. Alternatively, it is possible to use both flame inputs - each with its own independent UV sensor - to monitor the same flame, in this case permanent operation with signal redundancy is obtained. If the pilot burner flame is monitored via UV, but is only active during main burner ignition or for a period of less than 24 hours, a pilot flame monitoring shutter is not required, as it is not in permanent operation. If the main burner flame is monitored via UV, but is active for less than 24 hours, a main flame monitoring shutter is not required, as it is not in permanent operation. |