FLAME SUPERVISION |
|
The device supplies an isolated voltage of about 230VAC to power the sensors which, in the event of flame presence, produce a rectified current up to 60 µA. The signal is cancelled in the event of a short circuit or reversed polarity. The bar graph shows the intensity of the flame signal as a percentage value up to 100% according to what is selected in the configuration (parameter G06):
Typically phototubes produce higher signals than electrodes, but here the display is adapted to have uniform views. For multi-stage burners, different flame monitoring solutions can be adopted depending on the pilot burner behaviour: Alternating pilot An alternating pilot is extinguished at the end of the second safety time. Since the two flames are present at the same time only during the 2nd safety time, surveillance is allowed with a single sensor capable of detecting both, or with two sensors connected to the same input. Permanent pilot It means the pilot burner remains operative and will be shut off simultaneously with the main flame. In this case the two flames must be monitored independently, you need to use both flame input 1 and flame input 2 (EN 13577-2 § 4.10.1). For systems where the pilot burner remains in use during main burner operation, a separate flame detector device to supervise the pilot and main flames shall be fitted. |