MZ4a - 3 analog ACTUATOR

When the actuator is controlled via an analog signal directly from the temperature controller, the opening (ventilation) and closing (ignition) positions must be forced. The temperature controller maintains direct control of the actuator during all other stages of the operating cycle.


Elektrogas MZ4A

The wiring shown allows for the 

required operating logic

Elektrogas MZ4A.P1

The potentiometer is only for 

remote monitoring via fieldbus

For this mode, set the servomotor dip-switches to CONTROL TYPE: DUAL 2


Adjustment and Parameter Configuration:

  • Limit Switches: Set the maximum limit switch to the required pre-ventilation position and the minimum limit switch to the required ignition position.
  • Travel Time (G01): Configure parameter G01 with the maximum time required for the actuator to complete a full travel (alternatively, set it to the maximum value of 300 seconds).
  • Settings:
    -        Pre-purge: P03 = HI
    -        Post-purge: P11 = HI
    -        Pre-ignition: 003 = LO

All other parameters defining the actuator position during various operating stages (S03, L02, C04, 205, 305, 405, 505, 605, Y03) must be set to NO ACTION (default factory settings).