MZ4 - 3 POINTS ACTUATOR

In this configuration, the 3-point actuator is fully controlled by the Q2 unit, which determines the actuator position at each stage of the operating cycle. Except for the ventilation and ignition phases, the position can also be managed via fieldbus during all other operating stages.


Elektrogas MZ4

Wiring diagram for full position

control via Q2 unit

Elektrogas MZ4.P1

Potentiometer enables management of any intermediate position between limit switches

Adjustment and Parameter Configuration:

  • Limit Switches: Set the maximum limit switch to the required pre-ventilation position and the minimum limit switch to the required ignition position.
  • Travel Time (G01): Configure parameter G01 by entering the actual time required for the actuator to complete a          full travel. This configuration can be performed automatically by following the recommended procedure described below.
  • Typical settings:
    -        Pre-purge: P03 = HI
    -        Post-purge: P11 = HI
    -        Pre-ignition: 003 = LO

For other operating stages (S03, L02, C04, 205, 305, 405, 505, 605, Y03), specific positions can be defined, or the actuator can remain in its current position (default). Remote control is always available during these stages.


Recommended Procedure

For a quick setup, it is recommended to use the Commissioning utility in QSuite. This tool automatically scans the mechanical limits (limit switches) and the travel time; optionally, it allows for the definition of preferred positions for the various operating stages.


External temperature controller

If the actuator position is managed by an external temperature controller (TIC), refer to the wiring diagram provided at the beginning of the chapter.