- Any burner control equipment requires a ground system that provides a zero-voltage reference: the voltage measured from Neutral to all unpowered lines should be 0 volts.
- Run the ground wire in the same raceway as the hot and neutral from the main distribution service panel to burner control equipments and ensure that all metal parts are connected to ground.
- The power transformer and distribution cables must be sized to handle the inrush currents of the solenoid valves and ignition transformer: the voltage drop at the end of the line in the worst condition must be kept within 15% of nominal voltage.
- Typical 50/60Hz ground system has sufficient low-impedance at nominal frequency to maintain all metal surfaces at the same ground reference. But, this same system could be unable to provide this at higher frequencies because of the increased impedance caused by the SKIN EFFECT. At high frequencies surfaces are working better than solid cables: connect all metal surfaces of the kiln to improve the performance of the ground at high frequencies.
- A common distribution network is better than several independent cables routed to each equipment. The ground wire within multicore cables is not enough to provide proper grounding.
- All ground wires must be routed to a single ground point (star connection). The same should be made inside the equipment: route all ground wires to the ground screw on the equipment base, then a single ground pigtail should be provided between the ground screw on the equipment base and the equipment terminal board.
- All the equipment must be connected to a single point ground, using different ground connections could present a safety hazard.
- The earth ground wire must be capable of conducting high inrush and short circuit currents: an AWG13 / 2,5mm2 copper conductor is adequate but AWG11/4mm2 and wide straps or brackets are preferred.
- The ground path impedance must be less than 1 ohm. For a ground path to be low impedance at RF frequencies, the connection must be made with minimum length conductors having maximum surface areas. Since the ground is the return path for the ignition spark, this rule must be observed for the connection to burner heads (especially when electronic transformers are used).
- All ground connections should be free of non-conducting coatings and protected against rust.
- Utilizing conduit as an exclusive means of providing a ground must be avoided.
- Do not run high voltage ignition transformer wires in the same conduit with other wiring.
- Ensure the frame of the ignition transformer is securely connected to control panel frame and/or the burner frame. It is best to have the equipment, the ignition transformer and the burner on the same metal surface.
- When the ignition transformer is introducing excessive electromagnetic interferences (E/J errors) an additional transient suppressing device and/or filter could be installed from hot and neutral terminals of ignition transformer to ground.
- Periodically, the spark electrode should be inspected for proper gapping and cracked ceramics. Problems at high temperature may arise from electrode bending or ceramic degradation. An electrode cannot be considered reliable flame detector when the temperature is above 1000/1200 °C (1800/2200°F).
- Inspect neatness of wiring in junction boxes and cabinets. It is best to have connections short and direct. Avoid bunching-up and tying-off wires. Also connections should be periodically inspected for tightness and corrosion.
- Care must be taken not to route the control and communication cables in close proximity to any starter motor contactors located in the control panel or across any high voltage ignition wires.
- The use of a small busbar trunking system improves reliability and simplifies the installation.
|