HIGH TEMPERATURE MODE |
||||
|
During the start-up process, as long as the temperature of the combustion chamber walls is below 750°C, the flame surveillance must be active (low temperature mode). When the temperature rises above this spontaneous ignition temperature is possible to disable the direct flame surveillance: an external safety temperature controller activates the input at terminal HT entering the indirect flame control (high temperature mode). Parameter G08 defines whether the high temperature mode is activated immediately or at the next burner restart and also allows subordinating the HT input to an enabling sent with a remote control for those requiring further safety on the external signal. When the high temperature mode is active the last indicator of the flame signal bar graph flashes and the intensity of the flame signal is not reported. When the temperature falls below the spontaneous ignition temperature (750°C) the external temperature controller removes the voltage from terminal HT. Returning to low temperature operation the flame surveillance by means of UV sensor or flame rod is reinstated. Any failure to HT input leads to lockout. A failure of external temperature controller must remove the voltage from HT input.
|