FLAME SENSOR 1

Both UV phototubes and ionization electrodes (also shared with the ignition) can be connected to this flame input 1.

The use of a single shared electrode is not possible when the ignitor is activated during prepurge, postcombustion or post-purge.




Single stage burner

2 independent electrodes for ignition and ionization flame detection


Dual stage burner

2 independent electrodes for pilot ignition and detection + UV for main detection





Single stage burner

with shared electrode

for ignition and ionisation flame detection

During the ignition stage, the device connects terminals 09-10 together


Dual stage burner

with shared electrode

for ignition and ionization flame detection for pilot and UV phototube for main flame detection, both connected to the same input