DUAL STAGE - MODULATING |
||||||||||||||||||||||||||||||||||||||
|
The same connections can be used both for burners with a single high/low flame and for burners with independent pilot and main flame. For systems where the pilot burner remains in use during main burner operation, a separate flame detector device to supervise the pilot and main flames shall be fitted. Flame detection via single electrode [S] also used for ignition 2. A UV phototube [U] can be used for independent monitoring of the main flame. If the main burner remains operative for more than 24 hours consecutively, it will be necessary to use phototubes equipped with electro-optical shutters which guarantee permanent use. At the start of the cycle the air simulation test is performed before activating the air output [VA], if enabled. When the pressure switch A 1 detects the air pressure, the pre-purge time starts. During the pre-purge, no gas pressure must be detected and the flame simulation test is carried out. The fuel valve [V1] will only be activated if the behaviour of the ignition device [IT] matches with the settings. If a valid flame signal is detected within the programmed safety time, the valve is kept open: the burner is on. If no flame is detected there will be a lockout. In accordance with EN 13577-2 and EN676, up to 3 further ignition attempts are allowed if safety is not impaired. Three low temperature operating stages can be configured for each of which it is possible to define which valves are active. In this typical application there will be an initial period with only the pilot flame (stage 2 3) which can be followed by stage 3 3 with the pilot [V1] and main [V2] valve active. If an interrupted pilot is desired, this stage represents the second safety time before proceeding to stage 4 3 in which only the main valve V2 will be active. In the event of a flame, air or gas failure during operation, it is possible to set an immediate re-ignition, a complete recycle from the beginning or a lockout. The behaviour of the VB multifunctional valve can be configured in each stage to perform specific tasks, if required. The HT input activates the high temperature mode with exclusion of direct flame monitoring and step to stage 5 3, which may have a short duration and be used as a transition to any subsequent stage 6 3. The behaviour when the HT signal is removed is configurable (step to a low temperature stage, shutdown or recycling) in any case direct flame monitoring is reinstated. By starting the cycle with the HT signal present, at the end of the pre-purge the ignition stage will not be performed but you will proceed directly to stage 5. After a lockout or a shutdown request, a post-combustion time is allowed, possibly followed by post-purging. Reset from lockout can be done via front push button or with a remote control. To put the burner out of service (manual shutdown) press the button on the front panel during the operating cycle.
|
||||||||||||||||||||||||||||||||||||||
|
|
|
|
||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||||