SINGLE STAGE - DIRECT IGNITION - ON/OFF

To turn on/off the burner you can act directly on the power supply of the device or with remote control.
Air simulation test is carried out before to activate the air output [VA], if enabled.

When the pressure switch A 1 detects the air pressure, the pre-purge time starts.
During the pre-purge, no gas pressure must be detected and the flame simulation test is carried out.

The fuel valve [V1] will only be activated if the behaviour of the ignition device [IT] matches with the settings.

Flame detection by means of dedicated ionization electrode 2. If a valid flame signal is detected within the programmed safety time, the valve is kept open: the burner is on.

If no flame is detected there will be a lockout. In accordance with EN 13577-2 and EN676, up to 3 further ignition attempts are allowed if safety is not impaired.

In the event of a flame, air or gas failure during operation, it is possible to set an immediate re-ignition, a complete recycle from the beginning or a lockout.
After a lockout or a shutdown request, a post-combustion time is allowed, possibly followed by post-purging.

Reset from lockout can be done via front push button or with a remote control.

To put the burner out of service (manual shutdown) press the button on the front panel during the operating cycle.

1        If there is no air pressure switch, make a jumper between terminals A2-A3.

2        Permanent operation guaranteed when flame detection is carried out with an electrode.


A

AIR PRESSURE SWITCH

VA

AIR VALVE

G

FUEL PRESSURE SWITCH

VS

SAFETY VALVE

L

OPTIONAL EXTERNAL LIMITS

V1

FUEL VALVE

S

IGNITION ROD

R

FLAME DETECTTION ROD