SINGLE STAGE - DIRECT IGNITION - ON/OFF |
|||||||||||||||||
|
To turn on/off the burner you can act directly on the power supply of the device or with remote control. When the pressure switch A 1 detects the air pressure, the pre-purge time starts. The fuel valve [V1] will only be activated if the behaviour of the ignition device [IT] matches with the settings. Flame detection by means of dedicated ionization electrode 2. If a valid flame signal is detected within the programmed safety time, the valve is kept open: the burner is on. If no flame is detected there will be a lockout. In accordance with EN 13577-2 and EN676, up to 3 further ignition attempts are allowed if safety is not impaired. In the event of a flame, air or gas failure during operation, it is possible to set an immediate re-ignition, a complete recycle from the beginning or a lockout. Reset from lockout can be done via front push button or with a remote control. To put the burner out of service (manual shutdown) press the button on the front panel during the operating cycle. 1 If there is no air pressure switch, make a jumper between terminals A2-A3. 2 Permanent operation guaranteed when flame detection is carried out with an electrode. |
|||||||||||||||||
|
|
|
||||||||||||||||
|
|
|||||||||||||||||
|
|
||||||||||||||||