CONTROLLED SHUTDOWN

Settings that define the behavioUr of the device
after it receives a shutdown request

EN298 § 3.119

C01 – MINIMUM BURNER PAUSE TIME

In some processes it is necessary to prevent an immediate restart of the burner after a controlled shutdown, it is therefore possible to define a minimum pause time during which any restart requests will be ignored.

- 0 … 250 seconds (DEFAULT 0)

For oil burners without pre-purge the interval between shutdown and the next start attempt shall be more than 30 seconds.

EN298 § 7.101.2.7

C02 – FUEL VALVES

To adapt operation to different types of process, it is possible to define which fuel valves are active when the burner is in controlled shutdown.

- VB at terminal F6 (DEFAULT OFF)

In regenerative burners this could be the gas exhaust valve.

C03 – AIR VALVE

During this stage the air valve can be:

- OFF (DEFAULT)
- ON
- REMOTE CONTROL ONLY

C04 – ACTUATOR POSITION

When performing a controlled shutdown, it is possible to force the actuator into a predefined position:

- NO ACTION 3
- LO LIMIT SWITCH POSITION 1  (DEFAULT)
- HI LIMIT SWITCH POSITION 1
- POSITION 1 … 99 % 2 3

  1. Position cannot be changed by remote control
  2. Potentiometer must be connected
  3. Remote command may require a different position

C05 – AIR PRESSURE RESPONSE TIME

If the air valve is active during this stage (parameter C03) the contact of the air pressure switch must be closed, if it is open for a time longer than that set with this parameter there will be an air loss lockout.

If the air is inactive in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout.

- DISABLED (DEFAULT)
- 1 … 25 seconds

C06 – FUEL PRESSURE RESPONSE TIME

During this stage the fuel flow is stopped and the relative pressure switch must therefore be inactive, but a residual presence could be detected. This parameter allows you to define the maximum time within which the presence of fuel must no longer be detected before a lockout occurs.

- DISABLED (DEFAULT)
- 1 … 25 seconds

C07 – FLAME DETECTORS

While the burner is in controlled shutdown it is possible to carry out the flame simulation test, it is therefore necessary to define which sensors are active in this stage to detect an illegal flame.

- NONE
- FLAME 1 at terminal 10 (UV sensor or electrode)
- FLAME 2 at terminal 11 (UV sensor)
- FLAME 1+2 (DEFAULT)

EN298 § 7.101.2.9