ANALOG ACTUATOR CONTROL

Qio's analog output can control analog actuators or variable speed fans with a 4-20mA signal.

The trimmer [4] allows you to adjust the SPAN in the range 4 -19.0...22.5 mA.

When the actuator is controlled exclusively by Qio, each operating stage is associated with an analog output value, therefore a position / speed.
In this case the actuator is NOT controlled by Q2.

The factory default settings for the various stages are:

STANDBY

0 %

LOCKOUT

0 %

MANUAL SHUTDOWN

0 %

CONTROLLED SHUTDOWN

0 %

PREPURGE

100 %

PREIGNITION / IGNITION

0 %

STAGE 2 (PILOT ONLY)

50 %

STAGE 3 (PILOT + MAIN)

80 %

STAGE 4 (MAIN ONLY)

100 %

STAGE 5 (HI TEMP)

0 %

STAGE 6 (HI TEMP)

0 %

POSTCOMBUSTION

0 %

POSTPURGE

100 %

Advanced users can modify the output
by changing the operating rules


It is possible to use the HI and LO limit switches inputs to confirm that the purging and ignition positions have been reached before moving on to the next stage.

To achieve this behavior, the following parameters must be set

G01 – ACTUATOR MAX TRAVEL TIME
P03 – ACTUATOR POSITION DURING PREPURGE = HI
003 – ACTUATOR POSITION DURING IGNITION = LO
P11 – ACTUATOR POSITION DURING POSTPURGE = HI