AIR PRESSURE SWITCHES

The minimum air pressure switch is connected to terminals A1-A2.


If there is a pressure switch that detects excessive air pressure, it will be connected in series as shown in the figure.

The monitoring of the air pressure switch can be disabled or enabled in each stage (EN 13577-2 § 4.6.2 / NFPA 86 § 8.6.6), also setting the response time to compensate for delays in the formation of the correct pressure or unwanted interventions due to vibrations or other accidental phenomena.

The pressure switch that detects the minimum air pressure must always be installed downstream of the VA valve.


VFD controlled motor - NFPA 86 compliance

According to NFPA 86 § 8.6.3, variable frequency drives (VFDs) that control blowers required for combustion must be interlocked in the burner management system: an auxiliary contact from the starter must be wired in series with the air pressure switches to shut down in the event of a fault.

WAIT BEFORE PREPURGE

This input can also temporarily suspend the cycle while waiting for an external signal. 

For example, if the actuator is controlled externally, it is essential to wait for it to reach the required open position before proceeding with purge cycle (P contact).

The AIR PRESSURE RESPONSE TIME must be set to a value greater than the time required for the actuator to travel.


If pressure switches are present, they will be connected in series. The P contact must be kept closed in all phases in which the air pressure switch check is active.


The most correct method is the one illustrated in CENTRALIZED ACTUATOR.