UV SENSORS

The UV1 and UV4H sensors can be used for flame detection when the burner is intended for non-permanent use, i.e. when a shutdown is expected within 24 hours of operation.


The UV8 sensor incorporating an electro-optical shutter - controlled by Q2 - can be used for applications intended for permanent operation.


Both devices use a phototube that triggers an ionization process when hit by electromagnetic radiation: the electrons emitted by the negative electrode are captured by the positive electrode, producing a current flow.



Sensitivity shows no response in the visible region and is limited to a very narrow band of the ultraviolet spectrum typical of radiation by gas and oil flames.