STAGE 3 |
|
|
This stage is reached at the end of stage 2 or following a remote request. For operation with permanent pilot (always on) this stage could last until a shutdown or lockout occurs, and therefore will not have a predefined duration, while in the event of alternating pilot this can be set and represents the second safety time before the transition to stage 4. |
|
|
The behaviour of all fuel valves and the air valve can be defined. |
|
|
The actuator position can be preset and even changed remotely. The air pressure switch can be enabled to detect air failure or air simulation, depending on air output setting. The fuel pressure switch can be enabled to detect fuel failure. Response times of the air and fuel pressure switches are adjustable to tolerate short drops or spikes. |
|
|
The presence of flame is detected by one or both sensors. The reaction time to the flame loss can be set. |
|
|
If enabled, the electro-optical shutter periodically checks the correct operation of the UV sensor. Specific parameters define the behaviour in the event of flame quench, fuel pressure failure and air pressure failure: • lockout • re-ignition • recycle from the beginning If necessary, the post-combustion and post-purge stages will be performed before. |
|
|
|
|
|
This stage can be terminated by: • manual shutdown • controlled shutdown • lockout The transition to another low temperature stage can be requested with remote control. The transition to high temperature mode (stage 5) can take place immediately upon activation of the HT input or at next burner restart, according to parameter G08 |
|
|
It is also possible to define a minimum duration during which any controlled shutdown requests are ignored (for example to avoid too short operating periods in burners with impulse regulation. |
|
|
Allowed remote commands H R S s A a O o f L D d Dxx
2 4 |
|