Foundational
Requirement
|
SL-C Component Capability
|
Network Measures
|
SL-T Target Level Achieved
|
|
FR1 - IAC
Identification and Authentication Control
|
The device technically grants full access upon physical connection. Security relies only on physical barriers (enclosure) and procedure (power cycle), not user identity.
|
Isolated Interface
|
SL1
|
|
FR2 - UC
Use Control
|
Absence of authentication, no Role-Based Access Control (RBAC). The attacker gains full admin privileges. Disincentive is high because they cannot restore original parameters.
|
Isolated Interface
|
SL1
|
|
FR3 - SI
System Integrity
|
SL3: Integrity is guaranteed by the absolute physical confinement of the USB port and the point-to-point connection. Data transmission cannot be tampered with remotely.
|
Isolated Interface
|
SL3
Guaranteed by physical integrity
|
|
FR4 - DC
Data Confidentiality
|
SL3: Confidentiality is guaranteed by absolute physical segregation. Data is never exposed to a network or clear-text sniffing outside the secure enclosure.
|
Isolated Interface
|
SL3
Guaranteed by physical segregation
|
|
FR5 - RDF
Restricted Data Flow
|
SL4: The interface is permanently isolated from the network. The power-cycle procedure ensures configuration flow is strictly separated from operational flow.
|
Isolated Interface
|
SL4
Maximum possible restriction by design
|
|
FR6 - TRE
Timely Response to Events
|
The host records the communication failure (lockout event), creating an undeniable audit trail of the physical intrusion attempt.
|
Isolated Interface
|
SL3
Logging capability managed by the host. Assuming communication timeout has been enabled.
|
|
FR7 - RA
Resource Availability
|
SL3: Availability is secured by physical robustness and the procedural disincentive: any configuration change by an attacker will likely cause a system shutdown due to incorrect parameters, halting the attack.
|
Isolated Interface
|
SL3
Protected by physical and procedural robustness. Assuming communication timeout has been enabled
|