POSTPURGE Settings that define the behavioUr during pOSTpurge of combustion chamber EN298 § 3.115 |
|
|
|
P10 – AIR VALVE During this stage the air valve can be: - OFF Remote control is disabled. |
|
|
P11 – ACTUATOR POSITION When the postpurge starts, it is possible to force the actuator into a predefined position. The post-purge time starts after reaching the required position. - NO ACTION 3
|
|
|
P12 – POSTPURGE TIME Set postpurge time in forced draught burners according to relevant standards (EN 676). - 0 … 6000 seconds During this time the flame simulation test is carried out. The time starts when the actuator reaches the required position. EN298 § 3.124.6 |
|
|
P13 – AIR PRESSURE RESPONSE TIME If the air valve is active in this stage (parameter P10) the purge time will be counted only when the contact of the air pressure switch is closed for a time longer than that set with this parameter. If the contact is open for a time longer than that set with this parameter there will be an air loss lockout. If the air valve is disabled in this stage, the contact of the air pressure switch must be open, if it closes for a time longer than the one set with this parameter, there will be an air simulation lockout. - DISABLED (DEFAULT) |
|
|
P14 – FLAME DETECTORS During the post-purge it is possible to carry out the flame simulation test, it is therefore necessary to define which sensors are active in this stage to detect an illegal flame. - NONE (DEFAULT) EN298 § 3.108 – § 7.101.2.9 |
|
|
P15 – IGNITOR The relevant standards require that for oil burners the ignitor is active during postpurge. - OFF (DEFAULT) A shared electrode cannot be used for ignition and flame detection when the ignitor is activated during postpurge. EN298 § 7.101.3.3 |