LOCKOUTS

The red display reports the lockout origin while the blue one can provide further details, both flashing. 

LOCKOUT


detail


air

ERROR IN THE

AIR PRESSURE DETECTION


pressUre / flow failure

AIR PRESSURE OR FLOW NOT DETECTED

WHEN AIR OUTPUT IS ON





pressure / flow simulation

air pressure or flow detected

when air output is off


FUEL (GAS)

ERROR IN THE 

FUEL PRESSURE DETECTION


pressUre failure

FUEL pressure not detected

when SAFETY VALVE is on





pressure simulation

FUEL pressure detected

when SAFETY VALVE is oFF





proof of closure

INCOHERENT STATUS OF

SAFETY FUEL VALVE LIMIT SWITCH


oil HEATING

INSUFFICIENT TEMPERATURE DETECTED

BY THE FUEL HEATER THERMOSTAT


TIMEOUT / DROP

FAILURE TO PREHEAT

IN MAX ALLOWED TIME


ACTUATOR 

MALFUNCTION DETECTED

BY OPERATING THE ACTUATOR 


TIMEOUT

THE REQUESTED POSITION HAS NOT BEEN REACHED IN THE MAXIMUM TRAVEL TIME


ILLEGAL DETECTION

FLAME DETECTED

WHEN THE BURNER SHOULD BE OFF


DURING CONTROLLED SHUTDOWN

fLAME SIMULATION WHILE THE BURNER WAS IN CONTROLLED SHUTDOWN





DURING PREPURGE

fLAME SIMULATION during

PRE-OPERATION / PREPURGE





DURING POSTPURGE

fLAME SIMULATION during

POST-OPERATION / POSTPURGE





AT THE END OF POSTCOMBUSTION

FLAME STILL PRESENT AT THE END OF THE ALLOWED POSTCOMBUSTION TIME


UNSUCCESSFUL IGNITION

NO FLAME DETECTED AT THE END OF

1ST SAFETY TIME (IGNITION TRIAL)






FLAME LOSS

FLAME QUENCHING DURING

LOW TEMPERAURE OPERATION


DURING 2ND STAGE

THE FLAME SIGNAL IS MISSING

OR INSUFFICIENT





DURING 3RD STAGE

THE FLAME SIGNAL IS MISSING

OR INSUFFICIENT





DURING 4TH STAGE

THE FLAME SIGNAL IS MISSING

OR INSUFFICIENT


TIGHTNESS CONTROL

VALVE PROVING SYSTEM HAS DETECTED

A LEAKAGE IN THE FUEL VALVES


UPSTREAM VALVE

LEAKAGE DETECTED TO

VS FUEL SAFETY VALVE 





DOWNSTREAM VALVE(S)

LEAKAGE DETECTED TO

ONE OR MORE VALVES (V1 / V2 / Vb) 


REMOTE RESET

MORE THAN 5 ALLOWED REMOTE RESETS WITHIN 15 MINUTES






COMMUNICATION

INACTIVITY FOR A TIME LONGER

THAN THE SET TIMEOUT


TRAXBUS

MISSING COMMANDS

FROM SUPERVISORS





HOST

NO COMMUNICATION WITH

EXPANSION BOARD


CYBER ATTACK 

WRONG PASSWORD ATTEMPTING TO ACCESS THE FRONT IR INTERFACE


ACCESS DENIED

TO CONFIGURATION OR

COMMISSIONING ENVIRONMENTS


CYBER ATTACK 

WRONG PASSWORD ATTEMPTING TO ACCESS THE QNET WEBSERVER


ACCESS DENIED

AFTER 5 CONSECUTIVE ATTEMPTS WITH

THE WRONG PASSWORD


CYBER ATTACK 

WRONG PASSWORD ATTEMPTING TO ACCESS THE TRAXGATEWAY WEBSERVER


ACCESS DENIED

AFTER 5 CONSECUTIVE ATTEMPTS WITH

THE WRONG PASSWORD


CYBER ATTACK 

WRONG PASSWORD ATTEMPTING TO ACCESS THE QIO WEBSERVER


ACCESS DENIED

AFTER 5 CONSECUTIVE ATTEMPTS WITH

THE WRONG PASSWORD