CYCLE

The red display shows the step in progress while the blue one could provide possible additional indications on specific tasks.

step


TASK


MANUAL SHUTDOWN
unIT has been put out of service from push button. Push again to EXIT







STANDBY

WAITING FOR RESET WHEN PROGRAMMED FOR STANDBY MODE AT POWER-ON







CONTROLLED SHUTDOWN
THE BURNER HAS BEEN SHUT DOWN

BY REMOTE COMMAND




PAUSE TIME
IGNORE RESTART COMMANDS UNTIL THE END OF THE SET MINIMUM PAUSE TIME


AIR PRESSURE SWITCH TEST
AIR VALVE OFF: PRESSURE SWITCH MUST REACT CONSISTENTLY WITHIN 60 SECONDS




RELAYS TEST
CROSS CHECK OF OUTPUT AND

SAFETY RELAYS


PRE-OPERATION

PRE-ARRANGEMENT ACTIVITIES

BEFORE BURNER IGNITION




TIGHTNESS CONTROL

OPTIONAL FUEL VALVE TIGHTNESS TEST

IN PROGRESS






OIL PREHEATING

WAITS FOR THE FUEL TO REACH

THE REQUIRED IGNITION TEMPERATURE






AIR RUN-UP DELAY

OPTIONAL WAITING time

FOR air REACHING RATED flow






air waiting

INSUFFICIENT AIR

WAITING FOR PRESSURE OR FLOW SWITCH






actuator opening

THE ACTUATOR MOVES TO REACH THE REQUIRED POSITION FOR THE PREPURGE






actuator CLOSing

THE ACTUATOR MOVES TO REACH THE REQUIRED POSITION FOR THE PREPURGE






PREPURGE

PURGE OF COMBUSTION CHAMBER

IN PROGRESS


PRE-IGNITION

PREPARATION OF THE SETUP

FOR BURNER IGNITION




actuator CLOSing

THE ACTUATOR MOVES TO REACH THE REQUIRED POSITION FOR THE IGNITION






actuator opening

THE ACTUATOR MOVES TO REACH THE REQUIRED POSITION FOR THE IGNITION






SPARK ACTIVATION

TURN ON AND CHECK

THE CORRECT BEHAVIOUR OF THE IGNITOR






WAITING FOR FUEL pressUre

THE MINIMUM FUEL PRESSURE

IS NOT YET DETECTED


IGNITION

1ST SAFETY TIME

FUEL VALVE OPEN - WAITING FOR FLAME




FIRST ATTEMPT

3 MORE ATTEMPTS MAY FOLLOW

IN CASE of IGNITION FAILURE






SECOND ATTEMPT

2 MORE ATTEMPTS MAY FOLLOW

IN CASE of IGNITION FAILURE






THIRD ATTEMPT

1 MORE ATTEMPT MAY FOLLOW

IN CASE of IGNITION FAILURE






FOURTH ATTEMPT

LAST ALLOWED ATTEMPT LOCKOUT WILL FOLLOW IN CASE OF IGNITION FAILURE


STAGE 2

LOW TEMPERATURE

 TYPICALly PILOT ONLY or single stage













STAGE 3

LOW TEMPERATURE

TYPICALly PILOT & MAIN burner




ACTUATOR OPENING

THE ACTUATOR MOVES OPENING TO REACH THE REQUESTED POSITION








STAGE 4

LOW TEMPERATURE

TYPICAL MAIN ONLY (INTERRUPTED PILOT)




ACTUATOR CLOSING

THE ACTUATOR MOVES CLOSING TO REACH THE REQUESTED POSITION








STAGE 5

HIGH TEMPERATURE

TRANSITION STAGE




FORCED STAY

IGNORES SHUTDOWN COMMANDS UNTIL THE END OF THE MINIMUM DURATION TIME








STAGE 6

HIGH TEMPERATURE

OPERATING STAGE 







POST-COMBUSTION

WAITING FOR FLAME QUENCHING AFTER LOCKOUT OR SHUTDOWN REQUEST







POST-OPERATION

POST-ARRANGEMENT ACTIVITIES

AFTER BURNER SHUTDOWN 




TIGHTNESS CONTROL

OPTIONAL FUEL VALVE TIGHTNESS TEST

IN PROGRESS






air waiting

WAITING FOR RATED AIR PRESSURE BEFORE TO CONTINUE WITH PostPURGE






actuator opening

THE ACTUATOR MOVES TO REACH THE REQUIRED POSITION FOR THE POSTPURGE






actuator CLOSing

THE ACTUATOR MOVES TO REACH THE REQUIRED POSITION FOR THE POSTPURGE






POSTPURGE

PURGE OF COMBUSTION CHAMBER

IN PROGRESS