HISTORY

Below is the list of information returned by the device:


DEVICE

DEVICE OPERATING TIME - H00

The total time the device has been operational (powered on).

UP TO 99 YEARS

CYCLES DEPLOYED - H01

The total number of ignition cycles performed by the device

UP TO 4294967296 

BURNER OPERATING TIME - H02

The total time during which the burner has been operating.

UP TO 99 YEARS

LAST UNDERVOLTAGE - H03

Last deviation from the nominal voltage greater than -15%.

%

LAST OVERVOLTAGE - H04

Last deviation from the nominal voltage greater than +10%.

%

CONTROLLER TEMPERATURE - H05

Current temperature of the microcontroller 1 which supervises the regular performance of the functions performed by the device.

CELSIUS DEGREES

DEPLOYER TEMPERATURE - H06

Current temperature of microcontroller 2 which performs the functions related to the operating cycle.

CELSIUS DEGREES

CONTROLLER SUPPLY VOLTAGE - H07

Current value of the supply voltage of the microcontroller 1 which supervises the regular performance of the functions performed by the device.

VOLT

DEPLOYER SUPPLY VOLTAGE - H08

Current value of the supply voltage of the microcontroller 2 which performs the functions related to the operating cycle.

VOLT

POWER CYCLES - H19

The total number of times the device has been turned on (it is the number of times statistical information has been written to the device's flash memory).

UP TO 4294967296


VA - AIR VALVE

CYCLES DEPLOYED - H09

The total number of times the air valve has been turned on.

It can help develop a preventive maintenance plan for the valve and associated relay, which can be replaced before they fail.

UP TO 4294967296 

OPERATING TIME - H10

The total working time of the air valve (powered).

UP TO 99 YEARS


VS - SAFETY VALVE

CYCLES DEPLOYED - H11

The total number of times the safety valve has been turned on.

It can help develop a preventive maintenance plan for the valve and associated relay, which can be replaced before they fail.

UP TO 4294967296 

OPERATING TIME - H12

The total working time of the safety valve (powered).

UP TO 99 YEARS


VB - MULTIFUNCTION BYPASS VALVE

CYCLES DEPLOYED - H13

The total number of times the bypass valve has been turned on.

It can help develop a preventive maintenance plan for the valve and associated relay, which can be replaced before they fail.

UP TO 4294967296 

OPERATING TIME - H14

The total working time of the bypass valve (powered).

UP TO 99 YEARS


V1 - PILOT VALVE

CYCLES DEPLOYED - H15

The total number of times the pilot valve V1 has been turned on.

It can help develop a preventive maintenance plan for the valve and associated relay, which can be replaced before they fail.

UP TO 4294967296 

OPERATING TIME - H16

The total working time of the pilot valve V1 (powered).

UP TO 99 YEARS


V2 - MAIN VALVE

CYCLES DEPLOYED - H17

The total number of times the main valve V2 has been turned on.

It can help develop a preventive maintenance plan for the valve and associated relay, which can be replaced before they fail.

UP TO 4294967296 

OPERATING TIME - H18

The total working time of the main valve V2 (powered).

UP TO 99 YEARS


LOCKOUTS LOG

List of the last 39 lockouts or faults that have occurred and the time at which they occurred (referred to the device's operating time).

HOUR EVENT DETAIL