FRONT IR


Infrared/Optical Port used for local configuration via a dedicated USB optical adapter connected to a PC, assuming this interface is inaccessible from external networks.


Foundational

Requirement

SL-C
Component Capability

SL-C
Component Level Achieved

FR1 - IAC

Identification and Authentication Control 

The requirement is met via password access (something you know) combined with the physical adapter (something you have) and specific procedure (something you know). The password identifies the user/role.

SL2

Authentication is strong enough to resist generic attacks (SL2). Strength depends on password quality enforcement by the device firmware.

FR2 - UC

Use Control

The user is identified by the password), the device implements role-based access control (RBAC): specific password for configuration, specific password  for commissioning.

SL2/SL3

Relies entirely on the device's internal firmware and configuration tool to enforce role-based privileges based on the entered password.

FR3 - SI

System Integrity

The physical optical link provides intrinsic protection against sniffing/tampering on the wire. Integrity is further protected by basic communication protocols (e.g., checksum or redundant data).

SL3

The isolated, point-to-point connection and data redundancy strongly secures integrity against remote or easy internal attacks. 

FR4 - DC

Data Confidentiality

Data is transmitted via an isolated optical beam. While the data itself might not be encrypted, the physical confinement grants inherent confidentiality (no sniffing on the network).

SL2

Confidentiality is met due to physical isolation.

FR5 - RDF

Restricted Data Flow

Absolute Separation: The interface is completely disconnected from the network.

SL4

Physical isolation provides the highest level of flow restriction.

FR6 - TRE

Timely Response to Events

The device must log security events locally, including successful and failed login attempts and configuration changes, linked to the identified user/role. The incorrect password attempt is recorded in the device's memory.

SL3

failed access attempts (incorrect password entry) are recorded in the device's log memory


FR7 - RA

Resource Availability

Not susceptible to network DoS. Protected by physical access controls and firmware lockout mechanisms for password attempts. If an incorrect password is entered, the device enters lockout that makes the resource unavailable to both attacker and legitimate user upon the first violation.

SL3

Isolation prevents network-based DoS. Availability is protected by lockout mechanisms, with the device entering lockout and signaling with a specific code upon incorrect password entry.


The isolated infrared port design is a highly effective security-by-design strategy for local configuration and commissioning functions.

The interface meets or exceeds SL2 for all analyzed Foundational Requirements.

.