GUASTI

Il display rosso segnala il guasto rilevato mentre quello blu può fornire ulteriori dettagli, entrambi lampeggianti.

GUASTO


DETTAGLIO


USCITA NON OPERATIVA

L'USCITA DOVREBBE ESSERE ATTIVA

MA RIMANE INATTIVA


ACCENDITORE

NESSUNA TENSIONE DI FEEDBACK

RILEVATA ALL'USCITA DELL'ACCENDITORE





USCITA V1

NESSUNA TENSIONE DI FEEDBACK

RILEVATA ALL'USCITA DELLA VALVOLA V1





USCITA V2

NESSUNA TENSIONE DI FEEDBACK

RILEVATA ALL'USCITA DELLA VALVOLA V2





USCITA VB

NESSUNA TENSIONE DI FEEDBACK

RILEVATA ALL'USCITA DELLA VALVOLA Vb


CORTOCIRCUITO USCITA 

USCITA TROVATA ATTIVA 

MENTRE DOVREBBE ESSERE SPENTA


ACCENDITORE

TENSIONE DI FEEDBACK RILEVATA ALL'USCITA DELL'ACCENDITORE





USCITA V1

TENSIONE DI FEEDBACK RILEVATA ALL'USCITA DELLA VALVOLA V1





USCITA V2

TENSIONE DI FEEDBACK RILEVATA ALL'USCITA DELLA VALVOLA V2





USCITA VB

TENSIONE DI FEEDBACK RILEVATA ALL'USCITA DELLA VALVOLA Vb





RELE' MASTER DI SICUREZZA

È STATO RILEVATO UN CORTOCIRCUITO

DEL CONTATTO


RILEVAZIONE FIAMMA

MALFUNZIONAMENTO DI UN INGRESSO

O DI UN SENSORE DI FIAMMA


INGRESSO FIAMMA 1

SEGNALE INCOERENTE O FUORI PORTATA. SORVEGLIANZA FIAMMA INAFFIDABILE





INGRESSO FIAMMA 2

SEGNALE INCOERENTE O FUORI PORTATA. SORVEGLIANZA FIAMMA INAFFIDABILE





SENSORE 1

TEST CON OTTURATORE ELETTRO OTTICO FALLITO - SENSORE UV 1 INAFFIDABILE 





SENSORE 2

TEST CON OTTURATORE ELETTRO OTTICO FALLITO - SENSORE UV 2 INAFFIDABILE 





SENSORI 1 & 2

TEST CON OTTURATORE ELETTRO OTTICO FALLITO - ENTRAMBI I SENSORI INAFFIDABILI





AMPLIFICATORI DI FIAMMA

TEST PERIODICO FALLITO

AMPLIFICATORI DI FIAMMA INAFFIDABILI


INGRESSI

MALFUNZIONAMENTO DI UN INGRESSO DIGITALE DURANTE LA VERIFICA CONTINUA


PRESSOSTATO ARIA

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE 





PRESSOSTATO CARBURANTE (GAS)

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





ALTA TEMPERATURA (HT)

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





FEEDBACK ACCENDITORE 

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





FEEDBACK V1

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





FEEDBACK V2

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





FEEDBACK VB

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





INGRESSO PROOF OF CLOSURE

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





FINECORSA ATTUATORE 100%

TEST FAIL SAFE FALLITO

INGRESSO INAFFIDABILE





FINECORSA ATTUATORE 0%

FAIL SAFE TEST FAILED

UNRELIABLE INPUT





FINECORSA ATTUATORE

ENTRAMBI I FINECORSA

CHIUSI CONTEMPORANEAMENTE


 § PULSANTE

ATTIVO PER PIÙ

PIÙ DI 10 SECONDI






TENSIONE TROPPO ALTA

TENSIONE ALIMENTAZIONE OLTRE 110%

(REGISTRATO NELLA MEMORIA DEL LOG)


GRAVE

EVENTO SUPERIORE A 5 SECONDI

FUSIBILE È INTENZIONALMENTE BRUCIATO


§ TENSIONE TROPPO BASSA

TENSIONE ALIMENTAZIONE INFERIORE A 85%

(REGISTRATO NELLA MEMORIA DEL LOG)






§ PROGRAMMA

IL PROGRAMMA NON VIENE SVOLTO

NELLA SEQUENZA CORRETTA


JUMP 1

AVVENUTO AL MICROPROCESSORE 1

CONTROLLER





JUMP 2

AVVENUTO AL MICROPROCESSORe 2

DEPLOYER


§ MEMORIA

CORRUZIONE DEI DATI

In memoria


RAM 1

AVVENUTO AL MICROPROCESSORE  1

CONTROLLER





RAM 2

AVVENUTO AL MICROPROCESSORE  2

DEPLOYER





EEPROM

AVVENUTO ALLA MEMORIA DI BLOCCO

(NON VOLATILE)


§ MANCATA CORRISPONDENZA

COMPORTAMENTO CONTRADDITTORIO

DEI MICROCONTROLLORI






§ SISTEMA

MALFUNZIONAMENTO

MICROPROCESSORE


CRC 1

CORRUZIONE DEL FIRMWARE

MICROPROCESSORE 1 CONTROLLER





CRC 2

CORRUZIONE DEL FIRMWARE

MICROPROCESSORE 2 DEPLOYER





PARAMETRO NON VALIDO

VALORE NON CONSENTITO PER UN PARAMETRO DI CONFIGURAZIONE





CPU FAIL 1

TEST CPU FALLITO 

MICROPROCESSORE 1 CONTROLLER





CPU FAIL 2

TEST CPU FALLITO 

MICROPROCESSORE 2 DEPLOYER





WATCHDOG

ASSENZA DI COMUNICAZIONE TRA MICROPROCESSORI





TENSIONE TROPPO ALTA MCU

ALIMENTAZIONE LOGICA TROPPO ALTA FUSIBILE BRUCIATO SE DURA PIÙ DI 5" 





TENSIONE TROPPO BASSA MCU

ALIMENTAZIONE LOGICA

TROPPO BASSA





TEMPERATURA MCU

TEMPERATURA DI ESERCIZIO

FUORI DAL LIMITE





MEMORIA DI BLOCCO

MANCATA CORRISPONDENZA DATI

NELLA MEMORIA NON VOLATILE


§

GUASTI non ripristinabili 
SE IL GUASTO RIENTRA il funzionamento riprenderà alla successiva aLIMENTAZIONE